| 2013-12-11 14:52:23 | 114 SOUTH OLIVE AVENUE |
| | PERMIT #13060638 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| | (2009 EDITION WITH FLORIDA AMENDMENTS.) |
| | |
| | |
| | REPEAT COMMENT: SHEET A7.2.1.: THE STAIR GUARDRAILS FOR |
| | STAIR #1 ARE ONLY 30-INCHES TALL AND NEED TO BE AT |
| | LEAST 42-INCHES TALL. THE GUARDS SHALL BE MEASURED |
| | VERTICALLY ABOVE THE LEADING EDGE OF THE TREAD OR |
| | ADJACENT WALKING SURFACE. |
| | |
| | REPEAT COMMENT: SPRINKLER: PER FLORIDA ADMINISTRATIVE |
| | CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | REPEAT COMMENT: SPRINKLER: INDICATE THE LOCATION AND |
| | DISTANCE TO THE NEAREST FIRE HYDRANT. |
| | |
| | REPEAT COMMENT: SPRINKLER: FOR A FULLY SPRINKLERED |
| | BUILDING, A CLASS I FIRE PROTECTION STANDPIPE IS |
| | REQUIRED WHEN THE FLOOR LEVEL OF THE HIGHEST STORY IS |
| | LOCATED MORE THAN 30 FEET ABOVE THE LOWEST LEVEL OF |
| | FIRE DEPARTMENT VEHICHLE ACCESS. |
| | |
| | REPEAT COMMENT: ELEVATOR: PER SECTION 9.4.3 - FIRE |
| | FIGHTERS EMERGENCY OPERATIONS: ALL NEW ELEVATORS SHALL |
| | CONFORM TO THE FIRE FIGHTERS EMERGENCY OPERATIONS |
| | REQUIREMENTS OF ASME A17.1/CSA B44, SAFETY CODE FOR |
| | ELEVATORS AND ESCALATORS. |
| | |
| | PLUMBING: SHEETS P2.1-P2.3 INDICATE PLUMBING PIPING |
| | (RAIN LEADERS?) BEING ROUTED INTO AND DOWN THROUGH THE |
| | FIRE RATED EXIT STAIRS. PER SECTION NFPA 101 SECTION |
| | 7.1.3.2.1, PENETRATIONS INTO, AND OPENINGS THROUGH, AN |
| | EXIT ENCLOSURE ASSEMBLY SHALL BE LIMITED TO DOOR |
| | ASSEMBLIES FROM NORMALLY OCCUPIED SPACES AND CORRIDORS, |
| | REQUIRED EXIT DOOR OPENINGS, ELECTRICAL CONDUIT SERVING |
| | THE EXIT ENCLOSURE, DUCTWORK AND EQUIPMENT NECESSARY |
| | FOR INDEPENDENT STAIR PRESSURIZATION, WATER OR STEAM |
| | PIPING NECESSARY FOR THE HEATING OR COOLING OF THE EXIT |
| | ENCLOSURE, SPRINKLER PIPING, STANDPIPES, AND |
| | PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE |
| | CIRCUITS ARE INSTALLED IN METAL CONDUIT AND THE |
| | PENETRATIONS ARE PROTECTED. |
| | |