| 2013-07-01 14:41:38 | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. SHEET A 1.2 THE RESTROOMS HAVE 6 OR MORE REQUIRED |
| | FACILITIES. THE UNISEX RESTROON MAY BE USED IN THE |
| | REQUIRED FIXTURE COUNT FOR MALE OR FEMALE. |
| | 403.5 UNISEX TOILET AND BATHING ROOMS. |
| | IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE |
| | UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE |
| | OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS |
| | REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE |
| | WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE |
| | OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET |
| | ROOM REQUIREMENT. IN RECREATIONAL FACILITIES WHERE |
| | SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE |
| | UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED |
| | WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE |
| | INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED |
| | IN AN OCCUPANCY. |
| | |
| | 2. SHEET P 2.2 THE RAIN WATER LINES ARE NOT LABELED FOR |
| | SIZE OR SQUARE FEET. |
| | |
| | 3. SUMP PUMPS OR FLOOR DRAINS ARE REQUIRED IN ELEVATORS |
| | WITH FIREFIGHTERS' EMERGENCY OPERATION. THE DRAIN SHALL |
| | BE INDIRECT TO THE SANITARY. |
| | ASME A17.1 2.2.2.5 |
| | P 301.6 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS |
| | SHALL BE PERMITTED AT THE BASE OF THE SHAFT, PROVIDED |
| | THAT THEY ARE INDIRECTLY CONNECTED TO THE PLUMBING |
| | SYSTEM AND COMPLY WITH SECTION 1003.4. |
| | |
| | |