| 2013-06-26 14:50:07 | 114 SOUTH OLIVE AVENUE |
| | PERMIT #13060638 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| | (2009 EDITION WITH FLORIDA AMENDMENTS.) |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING ALL |
| | CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | SHEET LS1.1: PER SECTION 12.2.5.1.2, A DEAD-END IN AN |
| | ASSEMBLY OCCUPANCY SHALL NOT EXCEED 20 FEET AND THE |
| | COMMON PATH OF TRAVEL SHALL NOT EXCEED 20 FEET WHEN THE |
| | PATH SERVES MORE THAN 50 OCCUPANTS. |
| | |
| | SHEET A7.2.1.: THE STAIR GUARDRAIL DOES NOT APPEAR TO |
| | BE AT LEAST 42-INCHES TALL. |
| | |
| | SHEET ID1.2: DETAIL #12 (REFERENCED FROM SHEET A1.2) |
| | INDICATES THE STAIR GLAZING AS NON-FIRE RATED; HOWEVER, |
| | DETAIL #10 INDICATES THE GLAZING IS FIRE-RATED. |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED |
| | SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED |
| | IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE |
| | ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | SPRINKLER: PER FLORIDA ADMINISTRATIVE CODE SECTION |
| | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| | SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | SPRINKLER: INDICATE THE LOCATION AND DISTANCE TO THE |
| | NEAREST FIRE HYDRANT. |
| | |
| | SPRINKLER: FOR A FULLY SPRINKLERED BUILDING, A CLASS I |
| | FIRE PROTECTION STANDPIPE IS REQUIRED WHEN THE FLOOR |
| | LEVEL OF THE HIGHEST STORY IS LOCATED MORE THAN 30 FEET |
| | ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICHLE |
| | ACCESS. |
| | |
| | SHEET FS1.1: ALL THE FIRE SPRINKLER FLOOR PLANS ARE |
| | INDICATED AS "FIRE ALARM PLANS." |
| | |
| | SHEET E4.1: ALL THREE FLOOR PLANS ARE EXACTLY THE SAME. |
| | |
| | FIRE ALARM: PER SECTION 12.3.4.3.3, PROVIDE |
| | SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY |
| | OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300 |
| | OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY |
| | VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. |
| | |
| | FIRE ALARM: PROVIDE A PRE-RECORDED FIRE ALARM |
| | EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS |
| | BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT, |
| | AND EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE |
| | ELEVATOR. |
| | |
| | FIRE ALARM: INDICATE THE LOCATION OF THE FACP. NEW FIRE |
| | ALARM SYSTEMS SHALL BE FULLY ADDRESSABLE. A CERTIFICATE |
| | OF COMPLETION AND A THIRD PARTY MONITORING/VERIFICATION |
| | (UL OR ETL) CERTIFICATE SHALL BE PROVIDED AT TIME OF |
| | FINAL FIRE ALARM INSPECTION. PER LOCAL AHJ POLICY, DUCT |
| | SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM |
| | CONDITION. ELEVATOR RECALL SHALL BE INTERFACED WITH |
| | FIRE ALARM SYSTEM. |
| | |
| | ELEVATOR: PER SECTION 9.4.3 - FIRE FIGHTERS EMERGENCY |
| | OPERATIONS: ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTERS EMERGENCY OPERATIONS REQUIREMENTS OF ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS. |
| | |