| Notes |
| Date |
Text |
| 2013-07-30 14:32:25 | PROVIDE ARC-FLASH NOTICES AND WARNINGS PER NEC 110.16. | | | PROVIDE INTERSYSTEM BONDING POINT PER 250.94. BOND ALL | | | INTERIOR METAL PIPING SYSTEMS PER 250.94. PANEL B IS | | | 225A RATED AND PROTECTED AT 100A? LOAD IS REPRESENTED | | | AS 197A ON PANEL B. SEPARATE PERMITS REQUIRED FOR FIRE | | | ALARM, LOW VOLTAGE, DATA, TELEPHONE, AUDIO AND VIDEO | | | SYSTEMS, ETC. |
|