| Plan Review Notes For Permit 13060523 |
| Permit Number |
13060523 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-07-08 11:06:33 | MORSE GERIATRIC CENTER | | | 4847 FRED GLADSTONE DRIVE | | | 120 BED SKILLED NURSING REPLACEMENT | | | INSTALLATION OF ACCESS CONTROL EQUIPMENT | | | PERMIT # 13060523 | | | 2ND REVIEW | | | | | | 1. NO EQUIPMENT IS TO BE INSTALLED IN THE STAIRWELL. | | | ONLY APPROVED EQUIPMENT IS TO BE INSTALLED IN THE | | | STAIRWELLS. | | | | | | 2. ANY AND ALL DELAYED EGRESS INSTALLATIONS ON ANY AND | | | ALL EXIT DOORS SHALL COMPLY WITH THE FLORIDA FIRE | | | PREVENTION CODE 2010 EDITION, THE 101 LIFE SAFETY CODE, | | | CHAPTER 7 (DELAYED EGRESS) REQUIREMENTS. | | | | | | 3. LOW VOLTAGE INSTALLATIONS SHALL NOT INTERFERE WITH | | | ANY FIRE WALLS, SMOKE COMPARTMENTS, FIRE DAMPERS, ETC. | | | | | | 4. LOW VOLTAGE WORK (SECURITY EQUIPMENT) THAT IMPACTS | | | ANY MEANS OF EGRESS SHALL BE INSPECTED, TESTED, AND | | | APPROVED BY THE BUREAU OF FIRE PREVENTION. | | | | | | APPROVED PROVISO | | | | | | | | | | | | MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF | | | WEST PALM BEACH FIRE RESCUE | | | |
|