| 2013-06-20 06:58:44 | MORSE GERIATRIC CENTER |
| | 4847 FRED GLADSTONE DRIVE |
| | 120 BED SKILLED NURSING REPLACEMENT |
| | INSTALLATION OF ACCESS CONTROL EQUIPMENT |
| | PERMIT # 13060523 |
| | |
| | 1. NO CUT SHEETS PROVIDED FOR EQUIPMENT THAT IS PLANNED |
| | TO BE USED. THESE INCLUDE CARD READERS, SECURITY |
| | CAMERA'S, AND REMOTE DOOR RELEASES. |
| | |
| | 2. DRAWINGS NEED TO DESCRIBE COMPLIANCE FOR DELAYED |
| | EGRESS INSTALLATIONS ON ANY AND ALL EXIT DOORS. |
| | INSTALLATIONS ON EXIT DOORS SHALL COMPLY WITH THE |
| | FLORIDA FIRE PREVENTION CODE 2010 EDITION, THE 101 LIFE |
| | SAFETY CODE, CHAPTER 7 (DELAYED EGRESS) REQUIREMENTS. |
| | |
| | 3. WHAT IS DPS EQUIPMENT DESCRIBED ON THE DRAWINGS. |
| | |
| | 4. PLEASE DESCRIBE FUNCTION OF CARD READERS. |
| | |
| | 5. EQUIPMENT NOTED TO BE INSTALLED IN STAIRWELL # 1 AND |
| | 2. ONLY CERTAIN EQUIPMENT CAN BE INSTALLED IN |
| | STAIRWELLS. PLEASE PROVIDE MORE DETAILS. |
| | |
| | 6. REVISIONS THAT CONTAIN THE LETTER A ARE NOT |
| | IDENTIFIED IN THE PLAN REVIEW NOTES. |
| | |
| | 7. VALUE EXCEEDS 5,000.00 DOLLARS AND ARE NOT SIGNED |
| | AND SEALED. |
| | |
| | 8. PLEASE INDICATE ON PLANS WHICH DOORS THAT CAN BE |
| | CONSIDERED FAIL SAFE AND WHICH DOORS CAN BE IDENTIFIED |
| | AS FAIL SECURE. |
| | |
| | 9. PLEASE INDICATE HOW THESE LOW VOLTAGE INSTALLATIONS |
| | WILL NOT INTERFERE WITH ANY FIRE WALLS, SMOKE |
| | COMPARTMENTS, FIRE DAMPERS, ETC. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF |
| | WEST PALM BEACH FIRE RESCUE |