| 2013-07-10 12:23:10 | 13060446 | | | 1400 VILLAGE BLVD. | | | CLUBHOUSE RENOVATIONS | | | | | | PERMIT MAY BE ISSUED WITH THE FOLLOWING PROVISO: | | | | | | A SEPARATE ELECTRIC PERMIT IS REQUIRED FOR SITE | | | LIGHTING. | | | | | | PROVIDE SPECIFICATIONS AND THE LISTING FROM A | | | NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) FOR THE | | | POLES AND FIXTURES. NEC 110.3 | | | | | | PROVIDE WIND LOAD ENGINEERING FOR THE LIGHT POLES AND | | | FIXTURES. THE ENGINEERING DOCUMENT NEEDS TO REFERENCE | | | THE ACTUAL FIXTURE TYPE OR MODEL WITH ITS EPA AND ALSO | | | VERIFY THE EXISTING FOOTER IS STRUCTURALLY ADEQUATE. | | | FBC 1609.1 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | | | | |
|