| 2013-07-01 07:36:00 | BUILDING PLAN REVIEW |
| | PERMIT: 13060323 |
| | ADD: 400 N FLAGLER # 2004 |
| | CONT: CAMBRIDGE CONSTRUCTION |
| | TEL: (561)784-3722 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: 7/01/2013 |
| | ACTION: DENIED |
| | |
| | 1) DESCCRIPTION OF WORK INDICATES STRIPPING FLOORS AND |
| | NEW FLOOR TILE PROVIDE CODE COMPLIANCE FOR: |
| | FBC-B 2010 603.2 EXCEPTION (1) |
| | FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | |
| | 2) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | WHILE PROTECTO MAT MAY MEET THE SOUND REDUCTION |
| | REQUIREMENTS OF 1207.3 THIS PRODUCT DOES NOT MEET THE |
| | REQUIREMENTS OF 603.2 EXCETION # 1. 802.1 PROVIDES THE |
| | DEFINITION AND TESTING METHOD FOR FLAME SPREAD INDEX: |
| | 2010 FBC-B 802.1FLAME SPREAD INDEX. A COMPARATIVE |
| | MEASURE, EXPRESSED AS A DIMENSIONLESS NUMBER, DERIVED |
| | FROM VISUAL MEASUREMENTS OF THE SPREAD OF FLAME VERSUS |
| | TIME FOR A MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | |
| | 3-5) COMPLIED. |
| | |