| Plan Review Notes For Permit 13060319 |
| Permit Number |
13060319 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-20 09:22:45 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | SHEET A - 2 & DETAIL ON P - 1: THE RESTROOMS DO NOT, IN | | | THE SHOWN CONFIGURATION, MEET THE REQUIREMENTS OF THE | | | 2010 ACCESSIBILITY CODE. | | | THE LAVATORIES ARE WITHIN THE REQUIRED 60" CLEARANCE. | | | IN THE CONFIGURATION SHOWN THE WIDTH OF THE RESTROOM | | | WOULD BE 7'-1" MINIMUM. | | | | | | FBC ACCESSIBILITY 2010 604.3.1 SIZE. CLEARANCE AROUND A | | | WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM | | | MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES | | | (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR | | | WALL. | | | | | | 604.3.2 OVERLAP ...NO OTHER FIXTURES OR OBSTRUCTIONS | | | SHALL BE LOCATED WITHIN THE REQUIRED WATER CLOSET | | | CLEARANCE. | | | PLEASE SEE FIGURE 604.8.1.6 FOR EXAMPLE. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 |
|