2013-06-18 15:02:256651 NORTH JOG ROAD - ELECTRICAL ROOM
 PERMIT #13060277
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE BUILDING NAME OR ADDRESS ON THE
 BUILDING. NUMBERS/LETTERS SHALL BE ATTACHED TO THE
 BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH
 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 SHEET 100-EE-100: PLAN INDICATES BATTERY ROOM #101 (240
 SQ.FT.) TO BE A HAZARDOUS LOCATION. PER NFPA 101
 SECTION 7.11.4, NOT LESS THAN TWO MEANS OF EGRESS SHALL
 BE PROVIDED FROM EACH BUILDING OR HAZARDOUS AREA
 EXCEEDING 200 SQ.FT. PER SECTION 7.5.1.3.3, THE MINIMUM
 SEPARATION DISTANCE BETWEEN TWO EXITS OR EXIT ACCESS
 DOORS SHALL BE NOT LESS THAN ONE-HALF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA BEING SERVED.
  
 SHEET 100-A1.1: PANIC HARDWARE MAY BE NEEDED ON THE
 EXIT DOORS. PER NFPA 70 ARTICLE 110.26(C)(3): WHERE
 EQUIPMENT RATED 1200 A OR MORE THAT CONTAINS
 OVERCURRENT DEVICES, SWITCHING DEVICES, OR CONTROL
 DEVICES IS INSTALLED AND THERE ARE PERSONNEL DOORS
 INTENDED FOR ENTRANCE TO AND EGRESS FROM THE WORKING
 SPACE LESS THAN 25 FEET FROM THE NEAREST EDGE OF THE
 WORKING SPACE, THE DOORS SHALL OPEN IN THE DIRECTION OF
 EGRESS AND BE EQUIPPED WITH PANIC BARS, PRESSURE
 PLATES, OR OTHER DEVICES THAT ARE NORMALLY LATCHED BUT
 OPEN UNDER SIMPLE PRESSURE.
  
 SHEET 100-A1.1: ACCESS AROUND THE LARGE PIECE OF
 ELECTRICAL EQUIPMENT (NORTH PART OF SPACE) MAY BE
 NEEDED TO ELIMINATE THE DEAD-END WORKER SPACE CREATED
 BY THE EQUIPMENT.. PER NFPA 70 ARTICLE 110.26(C)(2):
 FOR EQUIPMENT RATED 1200 AMPERES OR MORE AND OVER 6
 FEET WIDE THAT CONTAINS OVERCURRENT DEVICES, SWITCHING
 DEVICES, OR CONTROL DEVICES, THERE SHALL BE ONE
 ENTRANCE TO AND EGRESS FROM THE REQUIRED WORKING SPACE
 NOT LESS THAN 24 INCHES WIDE AND 6.5 FEET HIGH AT EACH
 END OF THE WORKING SPACE. A SINGLE ENTRANCE TO AND
 EGRESS FROM THE REQUIRED WORKING SPACE SHALL BE
 PERMITTED WHERE EITHER OF THE CONDITIONS IN
 110.26(C)(2)(A) OR (C)(2)(B) IS MET.
  
 (A) UNOBSTRUCTED EGRESS. WHERE THE LOCATION PERMITS A
 CONTINUOUS AND UNOBSTRUCTED WAY OF EGRESS TRAVEL, A
 SINGLE ENTRANCE TO THE WORKING SPACE SHALL BE
 PERMITTED.
 (B) EXTRA WORKING SPACE. WHERE THE DEPTH OF THE WORKING
 SPACE IS TWICE THAT REQUIRED BY 110.26(A)(1), A SINGLE
 ENTRANCE SHALL BE PERMITTED. IT SHALL BE LOCATED SUCH
 THAT THE DISTANCE FROM THE EQUIPMENT TO THE NEAREST
 EDGE OF THE ENTRANCE IS NOT LESS THAN THE MINIMUM CLEAR
 DISTANCE SPECIFIED IN TABLE 110.26(A)(1) FOR EQUIPMENT
 OPERATING AT THAT VOLTAGE AND IN THAT CONDITION.
  
 SHEET 100-A1.1: VERY LITTLE INFORMATION PROVIDED FOR
 BATTERY STORAGE ROOM. DESIGN SHALL CONFORM TO NFPA 1 -
 CHAPTER 52 "STATIONARY STORAGE BATTERY SYSTEMS".
 PROVIDE ADDITIONAL INFORMATION SUCH AS THE BATTERY
 TYPES (FLOODED LEAD-ACID, FLOODED NICKEL-CADMIUM,
 LITHION-ION, VALVE REGULATED, ETC.), ELECTOLYTE
 CAPACITY, SPILL CONTROL ETC. LISTED BELOW ARE SOME ON
 THE REQUIREMENTS FROM NFPA 101 CHAPTER 52.:
  
 STATIONARY STORAGE BATTERY SYSTEMS HAVING AN
 ELECTROLYTE CAPACITY OF MORE THAN 100 GAL IN
 SPRINKLERED BUILDINGS OR 50 GAL IN UNSPRINKLERED
 BUILDINGS FOR FLOODED LEAD-ACID, NICKEL-CADMIUM, AND
 VALVE-REGULATED LEAD-ACID (VRLA) BATTERIES OR 1000 LB
 FOR LITHIUM-ION AND LITHIUM METAL POLYMER BATTERIES
 USED FOR FACILITY STANDBY POWER, EMERGENCY POWER, OR
 UNINTERRUPTED POWER SUPPLIES SHALL BE IN ACCORDANCE
 WITH CHAPTER 52 AND TABLE 52.1.
  
 52.3.4.1 ROOMS, BUILDINGS, OR AREAS CONTAINING
 FREE-FLOWING LIQUID ELECTROLYTE IN INDIVIDUAL VESSELS
 HAVING A CAPACITY OF MORE THAN 55 GAL OR MULTIPLE
 VESSELS HAVING AN AGGREGATE CAPACITY EXCEEDING 1000 GAL
 SHALL BE PROVIDED WITH SPILL CONTROL TO PREVENT THE
 FLOW OF LIQUIDS TO ADJOINING AREAS.
  
 52.3.8.1 DOORS OR ACCESSES INTO ROOMS, BUILDINGS, OR
 AREAS CONTAINING STATIONARY STORAGE BATTERY SYSTEMS
 SHALL BE PROVIDED WITH APPROVED SIGNS.
  
 52.3.8.2 THE SIGNS REQUIRED BY 52.3.8.1 SHALL STATE
 THAT THE ROOM CONTAINS STATIONARY STORAGE BATTERY
 SYSTEMS, THAT THE BATTERY ROOM CONTAINS ENERGIZED
 ELECTRICAL CIRCUITS, AND THAT THE BATTERY ELECTROLYTE,
 WHERE PRESENT, ARE CORROSIVE LIQUIDS.
  
 52.3.10 SMOKE DETECTION. AN APPROVED AUTOMATIC SMOKE
 DETECTION SYSTEM SHALL BE INSTALLED IN SUCH AREAS AND
 SUPERVISED BY AN APPROVED CENTRAL, PROPRIETARY, OR
 REMOTE STATION SERVICE OR A LOCAL ALARM THAT WILL GIVE
 AN AUDIBLE SIGNAL AT A CONSTANTLY ATTENDED LOCATION.
  