| 2013-08-02 16:54:53 | 9/26/13 RESPONDED TO EMAILS FROM MICHAEL SANCHEZ | | | REGARDING THE CLASSIFICATION OF THE BUILDING AND THE | | | SEPARATION OF AREAS. INFORMATION HAS BEEN PROVIDED | | | STATING "THE RECEPTACLES, LIGHT FIXTURES AND EXHAUST | | | FANS SERVING THE SPACE HAVE BEEN DESIGNED TO | | | ACCOMMODATE ?EXPLOSION PROOF DESIGN CRITERIA? AND ARE | | | NOTED AS SUCH ON THE DESIGN PLANS ALREADY SUBMITTED." | | | INFORMATION REGARDING THE BRAND, MODEL AND LISTING | | | INFORMATION FOR THE EQUIPMENT TO BE INSTALLED NEEDS TO | | | BE CALLED OUT ON THE PLANS AND THE CLASSIFIED AREAS OF | | | THE BUILDING NEED TO BE IDENTIFIED CLEARLY AND | | | DELINEATED AS TO WHICH SECTIONS ARE DEFINED AS | | | CLASSIFIED AND HOW THE OTHER AREAS ARE TO BE SEPARATED. | | | PLANS WILL BE PULLED AND RE-REVIEWED TO SEE IF THIS | | | INFORMATION WAS PROVIDED AND MISSED ON THE ORIGINAL | | | REVIEW. DH 6:50 AM | | | | | | 8/2/13 PLANS CALL FOR THIS ROOM TO BE RATED A SCLASS I, | | | DIV 2. PLEASE DEFINE THE HAZARD SO THE EQUIPMENT AND | | | LOCATIONS CAN BE PROPERLY EVALUATED. IT IS NOT KNOWN TO | | | THIS REVIEWER EXACTLY WHAT HAZARD IS ANTICIPATED OR | | | WHAT SPECIFIC GRAVITY OF HAZARD TO EVALUATE FOR. REVIEW | | | CANNOT BE COMPLETED UNTIL THESE QUESTIONS ARE ANSWERED. |
|