Plan Review Notes
Plan Review Notes For Permit 13060277
Permit Number 13060277
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-02 16:54:539/26/13 RESPONDED TO EMAILS FROM MICHAEL SANCHEZ
 REGARDING THE CLASSIFICATION OF THE BUILDING AND THE
 SEPARATION OF AREAS. INFORMATION HAS BEEN PROVIDED
 STATING "THE RECEPTACLES, LIGHT FIXTURES AND EXHAUST
 FANS SERVING THE SPACE HAVE BEEN DESIGNED TO
 ACCOMMODATE ?EXPLOSION PROOF DESIGN CRITERIA? AND ARE
 NOTED AS SUCH ON THE DESIGN PLANS ALREADY SUBMITTED."
 INFORMATION REGARDING THE BRAND, MODEL AND LISTING
 INFORMATION FOR THE EQUIPMENT TO BE INSTALLED NEEDS TO
 BE CALLED OUT ON THE PLANS AND THE CLASSIFIED AREAS OF
 THE BUILDING NEED TO BE IDENTIFIED CLEARLY AND
 DELINEATED AS TO WHICH SECTIONS ARE DEFINED AS
 CLASSIFIED AND HOW THE OTHER AREAS ARE TO BE SEPARATED.
 PLANS WILL BE PULLED AND RE-REVIEWED TO SEE IF THIS
 INFORMATION WAS PROVIDED AND MISSED ON THE ORIGINAL
 REVIEW. DH 6:50 AM
  
 8/2/13 PLANS CALL FOR THIS ROOM TO BE RATED A SCLASS I,
 DIV 2. PLEASE DEFINE THE HAZARD SO THE EQUIPMENT AND
 LOCATIONS CAN BE PROPERLY EVALUATED. IT IS NOT KNOWN TO
 THIS REVIEWER EXACTLY WHAT HAZARD IS ANTICIPATED OR
 WHAT SPECIFIC GRAVITY OF HAZARD TO EVALUATE FOR. REVIEW
 CANNOT BE COMPLETED UNTIL THESE QUESTIONS ARE ANSWERED.