Plan Review Notes
Plan Review Notes For Permit 13060271
Permit Number 13060271
Review Stop B
Sequence Number 2
Notes
Date Text
2013-08-01 17:37:16BUILDING PLAN REVIEW
 PERMIT: 13060271
 ADD: 3800 WASHINGTON # 1106
 CONT: BEE CUSTOM CONTRACTORS
 TEL: (954)802-7557
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:8/01/13
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) TILE FLOORS PROVIDE DOCUMENTATION TESTING FOR CODE
 COMPLIANCE WITH:
 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 1B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  