| Plan Review Notes For Permit 13060271 |
| Permit Number |
13060271 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-27 14:19:39 | 13060271 | | | 3800 WASHINGTON RD. #1106 | | | INTERIOR REMODEL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | INDICATE THE LOCATION OF THE ELECTRIC PANEL BOARD. | | | PROVIDE A PANEL SCHEDULE SHOWING THE NEW AND EXISTING | | | CIRCUITS. VERIFY THE REQUIRED WORKING CLEARANCES AND | | | DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR PANEL | | | BOARD. NEC 110.26, 240.24, 408.17 | | | | | | PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH | | | CIRCUITS. NEC 210.52 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. FBC 704.4.3 | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | |
|