Plan Review Notes
Plan Review Notes For Permit 13060271
Permit Number 13060271
Review Stop E
Sequence Number 1
Notes
Date Text
2013-06-27 14:19:3913060271
 3800 WASHINGTON RD. #1106
 INTERIOR REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE LOCATION OF THE ELECTRIC PANEL BOARD.
 PROVIDE A PANEL SCHEDULE SHOWING THE NEW AND EXISTING
 CIRCUITS. VERIFY THE REQUIRED WORKING CLEARANCES AND
 DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR PANEL
 BOARD. NEC 110.26, 240.24, 408.17
  
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. FBC 704.4.3
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  