| Plan Review Notes For Permit 13060229 |
| Permit Number |
13060229 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-06-24 14:30:14 | BUILDING PLAN REVIEW | | | PERMIT: 13060229 | | | ADD: 8170 OKEECHOBEE BLVD BLDG # 7 | | | CONT: ATLANTIC ENGINEERING SERVICES | | | TEL: (561)267-5941 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 3RD REVIEW | | | DATE: TUES. JUNE 24/ 2014 | | | ACTION: | | | BUILDING PROVISO | | | | | | DEFERRED SUBMITTALS: | | | 1A) ROOFING APPROVAL SUBMITTED NO SUBSYSTEM IDENTIFIED: | | | NOA: 13-0129.07 | | | JOHN MANVILLE BUILT-UP ROOFING OVER STEEL DECK. | | | NO SUB-SYTEM IDENTIFIED/ MAY REQUIRE ENHANCED | | | FASTENING. | | | LIMITATION # 7 REQUIRES DESIGN PROFESSIONAL FOR RAS 117 | | | CALCULATIONS. | | | | | | 1B) ROOFING APPROVAL SUBMITTED NO SUBSYSTEM IDENTIFIED: | | | NOA: 13-0129.19 | | | JOHN MANVILLE BUILT-UP ROOFING OVER STEEL DECK. | | | NO SUB-SYTEM IDENTIFIED/ MAY REQUIRE ENHANCED | | | FASTENING. | | | LIMITATION # 7 REQUIRES DESIGN PROFESSIONAL FOR RAS 117 | | | CALCULATIONS. | | | | | | 2) NO ROOF CURBING PRODUCT APPROVALS SUBMITTED, | | | DEFERRRED SUBMITTAL. | | | | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|