| 2013-11-05 08:58:35 | BUILDING PLAN REVIEW |
| | PERMIT: 13060229 |
| | ADD: 8170 OKEECHOBEE BLVD BLDG # 7 |
| | CONT: ATLANTIC ENGINEERING SERVICES |
| | TEL: (561)267-5941 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. NOV. 05/2013 |
| | ACTION: DENIED |
| | |
| | 1) THE SURVEY INDICATES THIS SITE IS LOCATED IN A AH |
| | FLOOD ZONE (EL 17'). THE CITY MUNI-CODE SECTION 94-546 |
| | (B)(2) NONRESIDENTIAL CONSTRUCTION DOES ALLOW FOR |
| | EITHER THE LOWEST FLOOR ELEVATION TO BE ELEVATED SIX |
| | INCHES HIGHER THAN THE BASE FLOOD ELEVATION OR, |
| | TOGETHER WITH THE ATTENDANT UTILITES AND SANITARY |
| | FACILITIES, BE FLOODPROOFED SO THAT BELOW THE SIX |
| | INCHES ABOVE THE BASE FLOOD LEVEL THE STRUCTURE IS |
| | WATER TIGHT. |
| | THREE FLOOD ZONE CERTIFICATES WILL BE REQUIRED DURING |
| | THE CONSTRUCTION PROCESS AND BEFORE A CERTIFICATE OF |
| | COMPLETION CAN BE ISSUED. |
| | 1A) THE FIRST FLOOD ELEVATION CERTIFICATE WILL BE THE |
| | PROPOSED FINISH FLOOR ELEVATION IN HGVD, THIS MUST BE |
| | TURNED IN BEFORE PERMIT ISSUANCE. |
| | 1B) THE SECOND FLOOD ELEVATION CERTIFICATE WILL BE |
| | REQUIRED AFTER THE FLOOR SLAB IS POURED. |
| | 1C) THE THIRD CERTIFICATE WILL BE REQUIRED PRIOR TO THE |
| | CERTIFICATTE OF COMPLETION, WITH THE HEIGHT OF ANY SLAB |
| | FOR A/C CONDENSORS. |
| | |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31,2015 |
| | |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015. |
| | THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL |
| | SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE |
| | FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING |
| | COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS |
| | CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED |
| | ON THE NEW FORM. |
| | |
| | ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW |
| | FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 2) COMPLIED. |
| | |
| | 3) 2ND REQUEST. IN THE NORTHWEST CORNER OF THE SURVEY |
| | AND NOTE # 7 INDICATE A PALM BEACH COUNTY UTILITY |
| | EASEMENT THAT IS TO BE VACATED, PLEASE SHOW |
| | DOCUMENTATION AS SUCH. 107.2.1 ADDITIONAL INFORMATION. |
| | LETTER RECEIVED FOR BUILDING 5 & 6 INDICATED THAT |
| | EASEMENTS TO BE VACATED AND NEW EASEMENTS TO BE |
| | SECURED. |
| | |
| | 4) 2ND REQUEST. SHEET A3 SOUTH ELEVATION SHOWS A |
| | PERCENTAGE OF OPENINGS (WINDOWS & DOORS), THE SURVEY |
| | INDICATES THE DISTANCE TO THE PROPERTY LINE IS 10.1 FT. |
| | PLEASE EITHER PROVIDE THE PER CENT AGE OF ALLOWABLE |
| | OPENINGS 10-15 FT , 45% UNPROTECTED OPENINGS OR WHAT |
| | ARRANGEMENT HAS BEEN MADE THAT TRACT A CAN NEVER BE |
| | SOLD AND THE AREA CAN BE COUNTED AS PART OF THE FIRE |
| | DISTANCE SEPERATION ? PLEASE PROVIDE DOCUMENTATION THAT |
| | THE PARKING LOT (74-42-43-29-30-001-0000) TRACT A CAN |
| | NEVER BE SOLD AND THE AREA CAN BE COUNTED AS PART OF |
| | THE FIRE DISTANCE SEPARATION? THE OWNERS MUST PRODUCE |
| | EITHER TYPE OF THESE TYPES OF DOCUMENTS, UNITY OF |
| | CONTROL, A RESTRICTIVE COVENANT OR A UNITY OF TITLE FOR |
| | THE AMOUNT OF OPENINGS AND THE CLOSENESS OF THE |
| | PROPERTY LINE SHOWN ON BOTH THE SURVEY AND THE PBC |
| | PROPERTY APPRAISERS WEB SITE. DIRECTLY SOUTH OF TRACT C |
| | IS COMMON TRACT A 8120 OKEECHOBEE BLVD PCN |
| | 74-42-43-29-30-001-0000. |
| | |
| | 5) 2ND REQUEST. SHEET A2 PLEASE PROVIDE CODE COMPLIANCE |
| | FOR 2010 FBC-ENERGY 502.2.3.1 SHELL BUILDINGS THIS |
| | SHEET LIST THE COMPONENTS THAT WILL MAKE UP THE ROOFING |
| | INSULATION. THE ENERGY CALCULATIONS INDICATE THE ROOF |
| | INSULATION TO BE A R16.0 THE ENERGY CODE UNDER THE |
| | PRESCRIPTIVE REQUIREMENTS FOR SHELL BUILDINGS SEE TABLE |
| | 502.1.1.1(1) INDICATE A R VALUE OF GREATER THAN OR |
| | EQUAL TO R40. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES |
| | SUBMITTED WERE (2) ROOFING PRODUCT APPROVALS FOR FLAT |
| | ROOFS |
| | NOA 13-0129.07 1OF 18 SHEETS NO SUB-SYSTEM IDENTIFIED |
| | SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM |
| | NOA 13-0129.19 1OF 38 SHEETS, NO SUB-SYSTEM IDENTIFIED |
| | SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM |
| | |
| | (E) PRE-ENGINEERED A/C STANDS |
| | |
| | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |