Plan Review Notes
Plan Review Notes For Permit 13060229
Permit Number 13060229
Review Stop B
Sequence Number 2
Notes
Date Text
2013-11-05 08:58:35BUILDING PLAN REVIEW
 PERMIT: 13060229
 ADD: 8170 OKEECHOBEE BLVD BLDG # 7
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: (561)267-5941
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: TUES. NOV. 05/2013
 ACTION: DENIED
  
 1) THE SURVEY INDICATES THIS SITE IS LOCATED IN A AH
 FLOOD ZONE (EL 17'). THE CITY MUNI-CODE SECTION 94-546
 (B)(2) NONRESIDENTIAL CONSTRUCTION DOES ALLOW FOR
 EITHER THE LOWEST FLOOR ELEVATION TO BE ELEVATED SIX
 INCHES HIGHER THAN THE BASE FLOOD ELEVATION OR,
 TOGETHER WITH THE ATTENDANT UTILITES AND SANITARY
 FACILITIES, BE FLOODPROOFED SO THAT BELOW THE SIX
 INCHES ABOVE THE BASE FLOOD LEVEL THE STRUCTURE IS
 WATER TIGHT.
 THREE FLOOD ZONE CERTIFICATES WILL BE REQUIRED DURING
 THE CONSTRUCTION PROCESS AND BEFORE A CERTIFICATE OF
 COMPLETION CAN BE ISSUED.
 1A) THE FIRST FLOOD ELEVATION CERTIFICATE WILL BE THE
 PROPOSED FINISH FLOOR ELEVATION IN HGVD, THIS MUST BE
 TURNED IN BEFORE PERMIT ISSUANCE.
 1B) THE SECOND FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED AFTER THE FLOOR SLAB IS POURED.
 1C) THE THIRD CERTIFICATE WILL BE REQUIRED PRIOR TO THE
 CERTIFICATTE OF COMPLETION, WITH THE HEIGHT OF ANY SLAB
 FOR A/C CONDENSORS.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) COMPLIED.
  
 3) 2ND REQUEST. IN THE NORTHWEST CORNER OF THE SURVEY
 AND NOTE # 7 INDICATE A PALM BEACH COUNTY UTILITY
 EASEMENT THAT IS TO BE VACATED, PLEASE SHOW
 DOCUMENTATION AS SUCH. 107.2.1 ADDITIONAL INFORMATION.
 LETTER RECEIVED FOR BUILDING 5 & 6 INDICATED THAT
 EASEMENTS TO BE VACATED AND NEW EASEMENTS TO BE
 SECURED.
  
 4) 2ND REQUEST. SHEET A3 SOUTH ELEVATION SHOWS A
 PERCENTAGE OF OPENINGS (WINDOWS & DOORS), THE SURVEY
 INDICATES THE DISTANCE TO THE PROPERTY LINE IS 10.1 FT.
 PLEASE EITHER PROVIDE THE PER CENT AGE OF ALLOWABLE
 OPENINGS 10-15 FT , 45% UNPROTECTED OPENINGS OR WHAT
 ARRANGEMENT HAS BEEN MADE THAT TRACT A CAN NEVER BE
 SOLD AND THE AREA CAN BE COUNTED AS PART OF THE FIRE
 DISTANCE SEPERATION ? PLEASE PROVIDE DOCUMENTATION THAT
 THE PARKING LOT (74-42-43-29-30-001-0000) TRACT A CAN
 NEVER BE SOLD AND THE AREA CAN BE COUNTED AS PART OF
 THE FIRE DISTANCE SEPARATION? THE OWNERS MUST PRODUCE
 EITHER TYPE OF THESE TYPES OF DOCUMENTS, UNITY OF
 CONTROL, A RESTRICTIVE COVENANT OR A UNITY OF TITLE FOR
 THE AMOUNT OF OPENINGS AND THE CLOSENESS OF THE
 PROPERTY LINE SHOWN ON BOTH THE SURVEY AND THE PBC
 PROPERTY APPRAISERS WEB SITE. DIRECTLY SOUTH OF TRACT C
 IS COMMON TRACT A 8120 OKEECHOBEE BLVD PCN
 74-42-43-29-30-001-0000.
  
 5) 2ND REQUEST. SHEET A2 PLEASE PROVIDE CODE COMPLIANCE
 FOR 2010 FBC-ENERGY 502.2.3.1 SHELL BUILDINGS THIS
 SHEET LIST THE COMPONENTS THAT WILL MAKE UP THE ROOFING
 INSULATION. THE ENERGY CALCULATIONS INDICATE THE ROOF
 INSULATION TO BE A R16.0 THE ENERGY CODE UNDER THE
 PRESCRIPTIVE REQUIREMENTS FOR SHELL BUILDINGS SEE TABLE
 502.1.1.1(1) INDICATE A R VALUE OF GREATER THAN OR
 EQUAL TO R40.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 SUBMITTED WERE (2) ROOFING PRODUCT APPROVALS FOR FLAT
 ROOFS
 NOA 13-0129.07 1OF 18 SHEETS NO SUB-SYSTEM IDENTIFIED
 SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM
 NOA 13-0129.19 1OF 38 SHEETS, NO SUB-SYSTEM IDENTIFIED
 SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM
  
 (E) PRE-ENGINEERED A/C STANDS
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  