2013-11-04 12:19:47BUILDING PLAN REVIEW
 PERMIT: 13060228
 ADD: 8170 OKEECHOBEE BLVD BLDG #5& 6
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: (561)267-5941
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: JULY 10/2013
 ACTION: DENIED
  
 1) 2ND REQUEST!!!!!THE SURVEY INDICATES THIS SITE IS
 LOCATED IN A AH FLOOD ZONE (EL 17'). THE CITY MUNI-CODE
 SECTION 94-546 (B)(2) NONRESIDENTIAL CONSTRUCTION DOES
 ALLOW FOR EITHER THE LOWEST FLOOR ELEVATION TO BE
 ELEVATED SIX INCHES HIGHER THAN THE BASE FLOOD
 ELEVATION OR, TOGETHER WITH THE ATTENDANT UTILITES AND
 SANITARY FACILITIES, BE FLOODPROOFED SO THAT BELOW THE
 SIX INCHES ABOVE THE BASE FLOOD LEVEL THE STRUCTURE IS
 WATER TIGHT.
 THREE FLOOD ZONE CERTIFICATES WILL BE REQUIRED DURING
 THE CONSTRUCTION PROCESS AND BEFORE A CERTIFICATE OF
 COMPLETION CAN BE ISSUED.
 1A) THE FIRST FLOOD ELEVATION CERTIFICATE WILL BE THE
 PROPOSED FINISH FLOOR ELEVATION IN HGVD, TO BE PROVIED
 TO THE CITY BEFORE PERMIT ISSUANCE.
 1B) THE SECOND FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED AFTER THE FLOOR SLAB IS POURED.
 1C) THE THIRD CERTIFICATE WILL BE REQUIRED PRIOR TO THE
 CERTIFICATTE OF COMPLETION, WITH THE HEIGHT OF ANY SLAB
 FOR A/C CONDENSORS.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2)SEMI-COMPLIED. SHEET A1 INDICATES THIS BUILDING WAS
 DESIGNED AS A TYPE 5B UNSPRINKLERED BUILDING, THE PLANS
 REFERENCE TABLE 503 , MERCANTILE AND ALLOWED AREA AS
 13,200 SQ FT. PLEASE REVIEW THE 2010 FBC-B TABLE 503,
 MERCANTILE ONLY ALLOWS 9,000 SQ FT FOR A TYPE VB
 -UNSPRINKLERED BUILDING. PLEASE REVIEW FBC-B 903.2.7
 (1) MERCANTILE WITH FIRE AREAS THAT EXCEED 12,000 SQ FT
 REQUIRE FIRE SPRINKLERS. PLEASE NOTE THE BUILDING
 FOOTPRINT OR AREA IS TAKEN FROM THE INTERIOR SIDE OF
 THE EXTERIOR WALL, OR APPROXIMATELY 12,902 SQ FT. THIS
 STILL EXCEEDS THE 9,000 SQ FT ALLOWED BY TABLE 503.1.
 IF THE DESIGNER WISHES TO TAKE BUILDING AREA
 MODIFICATIONS FOR FRONTAGE INCREASE (506.2) PLEASE
 PROVIDE THE FORMULA ON THE PLANS AND STATE AS SUCH,
 AREA INCREASE TAKEN.
  
 THIS PERMIT IS FOR THE BUILDING OF BUILDINGS 5 & 6
 CONNECTED BY A (4) HOUR FIRE WALL. THE ISSUE IS THE
 PROPERTY APPRAISERS OFFICE INDICATES AS WELL AS THE
 SURVEY THE TWO BUILDINGS ARE ON 2 SEPARATE PARCELS OF
 LAND, BLDG # 5 ONTRACT E 74-442-43-29-30-005-0000 AND
 BLDG # 6 ON TRACT 74-42-43-29-30-004-0000. AUNITY OF
 TITLE WIL BE REQUIRED TO UNIT THESE 2 TRACTS OF LAND SO
 THERE WILL BE NO PROPERTY LINE BETWEEN THEM.
  
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 3) 2ND REQUEST, IN THE RESPONSE LETTER IT DOES STATE
 THAT A NEW EASEMENT IS TO BE SECURED. IN THE WEST SIDR
 OF THE SURVEY AND NOTE # 7 INDICATE A PALM BEACH COUNTY
 UTILITY EASEMENT THAT IS TO BE VACATED, PLEASE SHOW
 DOCUMENTATION AS SUCH. 107.2.1 ADDITIONAL INFORMATION.
  
 4A) 2ND REQUEST, SHEET A3 EAST ELEVATION SHOWS A
 PERCENTAGE OF OPENINGS (WINDOWS & DOORS), THE SURVEY
 INDICATES THE DISTANCE TO THE PROPERTY LINE IS 9.6 FT.
 PLEASE EITHER PROVIDE THE PER CENT AGE OF ALLOWABLE
 OPENINGS 5-10 FT , 10% UNPROTECTED OPENINGS OR WHAT
 ARRANGEMENT HAS BEEN MADE THAT TRACT A CAN NEVER BE
 SOLD AND THE AREA CAN BE COUNTED AS PART OF THE FIRE
 DISTANCE SEPERATION? THE OWNERS MUST PRODUCE EITHER
 TYPE OF THESE TYPES OF DOCUMENTS, UNITY OF CONTROL, A
 RESTRICTIVE COVENENT OR A UNITY OF TITLE FOR THE AMOUNT
 OF QPENINGS AND THE CLOSENESS OF THE PREOPERTY LINE
 SHOWN ON BOTH THE SURVEY AND THE PBC PROPERTY
 APPRAISERS WEB SITE. DIRECTLY EAST OF TRACT D IS COMMON
 TRACT A 8120 OKEECHOBEE BLVD PCN
 74-42-43-29-30-001-0000.
  
 4B) 2ND REQUEST, BUILDING #6 TRACT D, SEE SURVEY FOR
 LOT LINE TO BUILDING DISTANCE (IRC LB # 7344) MARKERS
 SEE SURVEY. SHEET A3 SOUTH ELEVATION INDICATES WINDOWS
 IN THIS WALL SECTION THAT ARE 3.7 FT AWAY FROM THE
 PROPERTY LINE, THE WALL SHOWS COMPLIANCE WITH TABLE
 602, PLEASE SHOW CODE COMPLIANCE FOR OPENINING 3-5 FT
 FROM THE PROPERTY LINE, TABLE 705.8 NOT PERMITED FOR
 UNPROTECTED WINDOWS.
  
 4C) 2ND REQUEST, SHEET A2 THE EAST SIDE OF BUILDING # 5
 LOCATED ON TRACT E, SEE SURVEY INDICATES THE DISTANCE
 FROM THE PROPERTY LINE AS 6.2 FT AWAY, SHOW COMPLIANCE
 WITH ALLOWABLE OPENINGS FOR WINDOWS & A DOORS FROM THE
 PROPERTY LINE. PLEASE PROVIDE COMPLIANCE WITH FBC-B
 TABLE 705.8 10 % OPENINGS.
  
 5) 2ND REQUEST, SHEET A2 PLEASE PROVIDE CODE COMPLIANCE
 FOR 2010 FBC-ENERGY 502.2.3.1 SHELL BUILDINGS. THE
 ENERGY CALCULATIONS INDICATE THE ROOF INSULATION TO BE
 A R-40
 SHEET A2 INDICATES TYPES OF INSULATION TO BE INSTALLED
 PLEASE PROVIDE HOW THEY WILL ACHIEVE A R-40 VALUE, NOTE
 WITHIN THE ENERGY CALCULATIONS SUBMITED FOR SHELL
 BUILDINGS UNDER THE HEADING MATERIALS USED THERE ARE NO
 MATERIALS LISTED FOR THE ROOFING SHOWING A VALUE OF
 R40. 2010 FL ENERGY CODE TABLE 502.1.1.1(1). ENVELOPE
 PRESRIPTIVE MEASURES FOR SHELL BUILDINGS. THE PLANS
 SHOW MATERIAL TO BE INSTALLED BUT NOT IN THE ENERGY
 DOCUMENTS THAT PROVIDE THE R-VALUE FOR EACH COMPONENT.
  
 6)COMPLIED. SHEET A5 DETAIL # 1 THE PARAPET IS MISSING
 COPING. 2010 FBC-B PARAPET WALLS SHALL BE PROPERLY
 COPED WITH NONCOMBUSTIBLE, WEATHERPROOF MATERIALS OF A
 WIDTH NO LESS THAN THE THICKNESS OF THE PARAPET WALL.
 METAL COPING SHALL COMPLY WITH ANSI/SPRI ES-1 OR RAS
 111.
  
 7) SEMI-COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 8) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)((D) ROOFING PRODUCTS AND ASSEMBLIES
 SUBMITTED WERE (2) ROOFING PRODUCT APPROVALS FOR FLAT
 ROOFS
 NOA 13-0129.07 1OF 18 SHEETS NO SUB-SYSTEM IDENTIFIED
 SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM
 NOA 13-0129.19 1OF 38 SHEETS, NO SUB-SYSTEM IDENTIED
 SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM
 (E) PRE-ENGINEERED A/C STANDS
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER