Plan Review Notes
Plan Review Notes For Permit 13060228
Permit Number 13060228
Review Stop E
Sequence Number 1
Notes
Date Text
2013-07-02 12:22:52SEE SECOND REVIEW FOR ELECTRIC. RL
  
  
2013-06-21 12:02:028146-8160 OKEECHOBEE BLVD.
 PERMIT #13060228
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1. NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK
 INFORMATION.
 2. PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT SIGNS,
 EMERGENCY LIGHTING, PORTABLE FIRE EXTINGUISHERS.
 3. PLAN INDICATES SUITES 1-8, BUT NO FIRE RATED WALLS
 PROVIDED.
 4. THUMB-TURN LOCK TO BE EQUIPPED WITH A LOCK/UNLOCK
 INDICATOR.
 5. CONSTRUCTION TYPE IS REFERENCED TO BE TYPE VB,
 HOWEVER, PLANS DO NOT APPEAR TO BE WOOD FRAMED
 STRUCTURE.
 6. PLANS INDICATE NO TENANT SEPARATION WALLS AND THE
 AREA IS INDICIATED AT 13,200 SQ. FT OF MERCANTILE
 OCCUPANCY. PER NFPA 101 SECTION 36.3.5.1(2) STIPULATES
 THAT SPRINKLERS ARE REQUIRED FOR MERCANTILE AREAS
 EXCEEDING 12,000 SQ FT IN GROSS AREA.
 7. PROVIDE TACTILE SIGNAGE AT ALL EXIT DOORS.
 8. PLANS INDICATE TWO HYDRANTS ON THE SITE. PLEASE
 INDICATE ANY ADDITIONAL HYDRANTS THAT MAY BE LOCATED TO
 THE EAST AND SOUTH OF THIS BUILDING.
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  


Account Summary | Usage Policy | Privacy Policy