| 2013-07-11 08:33:57 | FAILED |
| | |
| | ALL COMPLIANT PLANS HAVE BEEN STAMPED BY ZONING; |
| | HOWEVER, NOT ALL THE REVISED PLANS ARE COMPLIANT. |
| | |
| | PLEASE PROVIDE WRITTEN RESPONSE TO COMMENTS. |
| | |
| | 1) NON-COMPLIANCE WITH THE DESIGN GUIDELINES: |
| | |
| | A. SHEETS C400, C403, C512, A100, A101, A111 & A200 DO |
| | NOT SHOW THE EXTENSION OF THE CURBED LANDSCAPE AREA ON |
| | THE WEST SIDE OF THE TRANSFORMER TO CONFORM WITH THE |
| | LANDSCAPE REQUIREMENTS ACROSS FROM A SERVICE COURT |
| | OPENING. |
| | B. THERE IS NOW A 15 TON RTU BEING PROPOSED FOR THE |
| | OUTLET CENTER ON BUILDING J-4. PROVIDE AN UPDATED LINE |
| | OF SIGHT STUDY TO VERIFY THAT THE UNITS ARE SCREENED AS |
| | REQUIRED BY THE DESIGN GUIDELINES. ADDITIONALLY, PLEASE |
| | ADD THE SPECIFICATIONS TO THE UNIT TO THE TABLE |
| | INCLUDED WITH THE COVER SHEET OF THE ORIGINAL LINE OF |
| | SIGHT STUDY. |
| | C. THE EASTERNMOST RTU ON BUILDING J7 HAS BEEN |
| | INCREASED TO 12.5 TONS. PROVIDE AN UPDATED LINE OF |
| | SIGHT STUDY TO VERIFY THAT THE UNIT IS SCREENED AS |
| | REQUIRED BY THE DESIGN GUIDELINES. |
| | D. A NEW SWITCH CABINET IS SHOWN ON SHEET A207. NO |
| | INFORMATION AS TO THE HEIGHT OF THIS CABINET WAS |
| | PROVIDED TO VERIFY THAT THE 7 FOOT WALL WILL BE TALL |
| | ENOUGH TO SCREEN THE EQUIPMENT. |
| | |
| | 2) INCONSISTENCIES WITH THE LATEST FORMAL SITE PLAN |
| | (CURRENTLY UNDER REVIEW) WHICH IS TO BE THE PLAN THAT |
| | INCLUDES ALL OF THE CONSTRUCTION CHANGES TO DATE: |
| | |
| | A. SHEETS C400, C401, C402, C510, C511, A100, A101, |
| | A111, A112, A201, A203 AND A205 SHOW INCORRECT |
| | LOCATIONS AND/OR NUMBER OF BICYCLE RACKS WHEN COMPARED |
| | TO THE RECENTLY SUBMITTED FORMAL SITE PLAN REVISIONS. |
| | B. SHEETS A100, A101, A111, A202 SHOW THE TR/REC AREA |
| | WITHIN THE BUILDING J3 SERVICE COURT IN A DIFFERENT |
| | LOCATION THAN THE FORMAL SITE PLAN REVISIONS. |
| | C. SHEETS A100, A101, A200 AND A300 SHOW DOORWAYS NOT |
| | SHOWN ON THE FORMAL SITE PLAN REVISIONS. |
| | |
| | 3) SHEETS A224.1 BUILDING J5 ROOF PLAN SHOWS AN 8.5 TON |
| | RTU IN THE SAME SPAT THAT SHEET M208 SHOWS A 10 TON |
| | RTU. ALL PLANS SHALL SHOW THE SAME CONDITIONS. |
| | |
| | NOTE - THE CIVIL SHEETS (DRAINAGE PLANS) SHOW MORE THAN |
| | THE SCOPE OF WORK FOR THE OUTLET BUILDING. THE DRAINAGE |
| | AND UTILITY PLANS SHALL BE SUBMITTED TO THE ENGINEERING |
| | SERVICES DEPARTMENT FOR REVIEW. |
| | |