| 2013-09-26 08:33:28 | BUILDING PLAN REVIEW |
| | PERMIT: 13060215 |
| | ADD: 7050 S DIXIE HWY SUITE # 100 |
| | CONT: ALDBRIGE |
| | TEL: (561)309-9749 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SEPT. 26/ 2013 |
| | ACTION: PROVISO |
| | BUILDING APPROVED WITH EXCEPTION! THIS PLAN HAS BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL |
| | RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT OF |
| | RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL |
| | REVIEWS WITH ASSOCIATED FEES. |
| | |
| | CONTRACTOR LISTED DISPROPORTION COST LIST, TOTAL |
| | EXPENDITURES OF $24,000.00 HAD A TOTAL DISPROPORTIONATE |
| | COST OF $6,150.00 OF THAT MONIES SPENT WERE UPGRADES OF |
| | $2,500.00 UPGRADES TO THE ELECTRICAL, THIS UPGRADE WAS |
| | REQUIRED BY THE 2008 NEC SECTION 517.18 AND CAN NOT BE |
| | COUNTED AS PART OF THE 20% UPGRADES UNDER THE 2010 |
| | FLORIDA ACCESSIBILITY CODE. AN ADDITIONAL $1,150.00 |
| | WILL NEED TO BE SPENT IN ACCESSIBLE UPGRADES, PLEASE |
| | SUBMIT WHERE THESE ADDITIONAL FUNDS ARE TO BE SPENT TO |
| | MEET THE |
| | 20 % DISPROPORTION COST. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |