| Permit Number |
13060204 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-25 12:26:26 | PERMIT ISSUED WITH THE FOLLOWING PROVISO: | | | | | | LOW VOLTAGE DATA CONDUCTORS ARE REQUIRED TO BE | | | SEPARATED FROM THE POWER CONDUCTORS WITHIN A | | | NONCONDUCTIVE SLEEVE. NEC 725.136 (D)(2) | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6718 | | | |
|