Plan Review Notes
Plan Review Notes For Permit 13060101
Permit Number 13060101
Review Stop B
Sequence Number 4
Notes
Date Text
2013-08-05 09:55:52BUILDING REVIEW APPROVED WITH PROVISO:
 1- SOIL TEST REPORT SAYS "ALLOWABLE BEARING PRESSURE OF
 1,500 PSF". WHILE, ARCHITECT SPECIFIES ON THE
 FOUNDATION PLAN "SOIL BEARING CAPACITY MIN. 2500 PSF".
 EXISTING SOIL WILL NOT SUPPORT PROPOSED STRUCTURE. THIS
 NEEDS TO BE ADDRESSED BY THE ARCHITECT OF RECORD OR BY
 THE GEO-TECHNICAL ENGINEER.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) GARAGE
 DOOR. NOA 12-0110.12 SUBMITTED EXPIRED ON MARCH 10,
 2013. B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, DETAILS, SECTIONS AND SPECIFICATIONS. ONLY TWO
 CONNECTORS WERE SUBMITTED. C) PRECAST LINTELS. NOA
 11-0121.04 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE.
  
 3- ARCHITECT TO REVIEW AND APPROVE ABOVE PRODUCT
 APPROVALS.
  
 4- ARCHITECT TO SPECIFY ON PLANS DEAD LOADS, LIVE
 LOADS, AND THE ATTIC LIVE LIVE LOADS AS REQUIRED BY
 SEC. R301.1 AND TABLE R301.5 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: SPECIFY EACH LOAD NOT JUST THE TOTAL LOADS.
  
 5- WALL SECTION ON SHEET 6 OF 6: CLARIFY WHAT IS "NO
 UN-INSULATED VENTED ATTIC"?. IS IT VENTED OR NOT???.
  
 6- SPECIFY R-VALUE IN WALL INSULATION. SEE ENERGY
 CALCULATIONS.