| Plan Review Notes For Permit 13060101 |
| Permit Number |
13060101 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-07-24 14:51:41 | RESIDENTIAL (R3) ADDITION, SECOND PLUMBING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- REVISED PLUMBING RISER DIAGRAM SUBMITTED DOESN'T | | | COMPLY WITH THE VENTING REQUIREMENTS OF SEC. P3108.2.1 | | | OF 2010 FBC-RESIDENTIAL. "NOT MORE THAN ONE WET-VENTED | | | FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE | | | DRY-VENTED FIXTURE DRAIN CONNECTION". REVISED PLUMBING | | | RISER DIAGRAM SHOWS THE TUB AND SHOWER UPSTREAM OF THE | | | DRY-VENT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|