Plan Review Notes
Plan Review Notes For Permit 13060101
Permit Number 13060101
Review Stop B
Sequence Number 1
Notes
Date Text
2013-06-19 16:52:52RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF THE PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE
 COUNTY IMPACT FEE UNIFIED LAND DEVELOPMENT CODE.
  
 2- CARPORT AREA SHEET 3 OF 6:
 A) PLANS SHOW INSTALLATION OF NEW GARAGE DOOR IN THE
 CARPORT. THIS WILL AFFECT THE STRUCTURAL STABILITY OF
 THE HOUSE. THE HOUSE WAS DESIGNED FOR AN OPEN CARPORT.
 THE NEW FRONT WALL AND GARAGE DOOR WILL CREATE MORE
 WIND LOADS TO THE ROOF ABOVE CARPORT AND SIDE WALLS.
 PROVIDE ENGINEERING ANALYSIS FOR THE PROPOSED
 INSTALLATION. AND, PROVIDE COMPLETE SPECS AND DETAILS
 SHOWING REINFORCEMENT, IF REQUIRED TO RESIST THE
 ADDITIONAL LOADS. SEC. 107.2.1.3 CITY AMENDMENTS TO
 FBC. ALSO, COORDINATE WITH ITEM #3 BELOW.
  
 B) PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THE
 GARAGE DOOR STRUCTURAL BUCK DETAIL ATTACHMENT. THIS IS
 THE DESIGNER OF RECORD RESPONSIBILITY, NOT THE PRODUCT
 APPROVALS AS SPECIFIED ON "GARAGE DOOR BUCKS" NOTE ON
 SHEET 3 OF 6. STRUCTURAL BUCK DETAIL TO RESIST THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) GARAGE DOOR AS SHOWN ON PLANS. *** NOTE: NEED
 PRODUCT APPROVAL FOR GARAGE DOOR THAT IS DESIGNED TO
 RECEIVE THE WIND LOADS FROM BOTH SIDES AS SHOWN ON
 PLANS. COORDINATE WITH ITEM #2 ABOVE.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, DETAILS, SECTIONS AND SPECIFICATIONS. ***NOTE:
 PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING SPECIFIED CONNECTOR.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL THE PRODUCT APPROVALS. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 5- SPECIFY ON PLANS CARBON MONOXIDE ALARMS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 6- A) SOIL TEST REPORT SUBMITTED IS INCOMPLETE. IS
 MISSING THE ENGINEERING INFORMATION CONTAINED IN A
 TYPICAL SOIL TEST REPORT. THE REPORT IS MISSING THE
 RECOMMENDATIONS FOR DESIGN, ESTIMATED SETTLEMENT, SOIL
 PREPARATION INCLUDING NEW FILL, ETC. SEC. 107.2.1.3
 CITY AMENDMENTS.
  
 B) ENGINEER SEALING THE REPORT TO USE CURRENT SEAL AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE. SEAL USED IS
 NO LONGER VALID SINCE JANUARY 2006.
  
 C) PROVIDE SOIL TEST REPORT (2 COPIES) WITH ORIGINAL
 ENGINEER'S SEAL AND SIGNATURE, NOT COPY. SEC. 471
 FLORIDA STATUTE.
  
 7- VALUED DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUES WAS UPDATED AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC. VALUATION TO INCLUDE SOIL
 PREPARATION, ALL LABOR AND MATERIALS, ALL PROFESSIONAL
 DESIGN FEES. ESTIMATED VALUE IS $83,040. PERMIT FEE
 BALANCE IS $2303.04.
  
 8- ARCHITECT TO SPECIFY ON PLANS ALL DEAD AND LIVE
 LOADS INCLUDING THE ATTIC LIVE LIVE LOADS AS REQUIRED
 BY SEC. R301.1 AND TABLE R301.5 OF 2010
 FBC-RESIDENTIAL.
  
 9- PROVIDE MANUFACTURER SPECS FOR THE ICYNENE
 INSULATION SPECIFIED ON PLANS AND ENERGY CALCULATIONS.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 10- SOIL TEST REPORT SUBMITTED STATES THAT SOIL BEARING
 CAPACITY IS 2,000 PSF. ARCHITECT'S PLANS AND DETAILS
 REQUIRE 2500PSF SOIL BEARING CAPACITY. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 11- SHEET 5 OF 6: A) REVISE ROOF SHEATHING NOTES: NEED
 TO SPECIFY MIN. 8D RING SHANK NAILS AT 4"-0" IN ROOF
 ZONE #3 AS REQUIRED BY SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL.
  
 B) IDENTIFY ROOF SHEATHING ZONES AS REQUIRED BY FIGURE
 R803.2.3.1 OF 2010 FBC-RESIDENTIAL. NOTE THAT GABLE END
 REQUIRES 5'-0".
  
 C) SPECIFY TRUSS CONNECTORS FOR TRUSSES THAT ARE GOING
 TO BE SUPPORTED ON EXISTING MASONRY WALL BY THE NEW
 WALK IN CLOSET. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- WALL SECTION ON SHEET 6 OF 6; A) CLARIFY IF ATTIC
 IS DESIGNED TO BE VENTED OR UNVENTED. SEC. R806 OF 2010
 FBC-RESIDENTIAL. THERE IS ONE NOTE SAYING "MATCH
 EXISTING SOFFIT & VENTS", BUT THERE ARE SPECIFICATIONS
 FOR ICYNENE INSULATION IN THE ATTIC. REVISE AS REQUIRED
 TO MATCH. COORDINATE WITH ENERGY CALCULATIONS
 SUBMITTED.
  
 B) IF DESIGNING VENTED ATTIC, THEN SPECIFY VENT SIZE
 AND SPACING. SEC. R806 OF 2010 FBC-RESIDENTIAL AND SEC.
 103 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) CLARIFY IF USING THE RIDGE VENT OR NOT. THERE WAS A
 PRODUCT APPROVAL SUBMITTED FOR RIDGE VENT. ARCHITECT TO
 SPECIFY ON PLANS THE RIDGE VENT IF USING IT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 D) IF DESIGNING UNVENTED ATTIC, THEN, SPECIFY R-VALUE
 FOR THE ICYNENE INSULATION. SEC. 103 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 F) SPECIFY R-VALUE IN WALL INSULATION. COORDINATE WITH
 ENERGY CALCULATIONS. SEC. 103 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 13- TRUSS PACKAGE (CHAPTER 471 FLORIDA STATUTE AND SEC.
 61G15-31.003):
 A) TRUSS ENGINEER TO PROVIDE TITLE BLOCK ON EACH SHEET.
  
 B) TRUSS ENGINEER TO USE CURRENT SEAL. SEAL USED IS NO
 VALID SINCE JANUARY 2006.
  
 C) ALL THE SHEETS NEED TO BE NUMBERED AND COORDINATED
 WITH COVER SHEET.
  
 D) TRUSS ENGINEER NEED TO UPDATE HIS LICENSE WITH DPBR.
  
 E) DESIGNER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE. PERSON WHO REVIEWED TRUSS PACKAGE IS NOT THE
 SAME SIGNING AND SEALING THE PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL