| Plan Review Notes For Permit 13060089 |
| Permit Number |
13060089 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-08 12:02:50 | | | | 13060089 | | | 438 36TH STREET | | | SF REMODEL ? 2 UNITS | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | SHOW THE ELECTRIC SERVICE AND PANEL BOARD LOCATIONS. | | | INDICATE THE FAULT CURRENT CAPABILITY OF THE ELECTRICAL | | | SERVICE DISCONNECTS AND PANEL BOARDS. INCLUDE PANEL | | | SCHEDULES. NEC 110.9, 215.5 | | | | | | BASED ON THE SUPPLIED ELECTRICAL CALCULATION THE | | | PROPOSED ELECTRIC SERVICE IS TOO SMALL. PLEASE CLARIFY. | | | NEC 230.31 | | | | | | THE ALUMINUM CONDUCTORS ARE UNDERSIZED. NEC T. 310.16 | | | | | | GROUNDING AND BONDING OF PANEL BOARDS AT SEPARATE | | | BUILDINGS SHALL INCLUDE AN EQUIPMENT GROUNDING | | | CONDUCTOR AND A GROUNDING ELECTRODE. NEC 250.32 (A) AND | | | (B) | | | | | | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS. | | | NEC 210.11 (C)(3) | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE | | | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A | | | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | | R313 | | | | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE | | | FRONT AND BACK ENTRANCE AREAS. NEC 210.52 (E) (1) | | | | | | A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE | | | GROUND NEC 250.94 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | | | | | | | |
|