| Notes |
| Date |
Text |
| 2014-03-03 16:08:00 | IMPORTANT PROVISO NOTICE: | | | THE ATTACHED CONDITIONS AND/OR RESTRICTIONS HAVE BEEN | | | MADE A PART OF THE CONDITIONAL APPROVAL OF THIS PERMIT | | | OR PLANS BY THE ELECTRICAL PLANS EXAMINER: | | | FBC-E 505.2.4 EXTERIOR LIGHTING: ALL EXTERIOR LIGHTING | | | NOT EXEMPTED BY 505.1 SHALL HAVE AUTOMATIC CONTROLS TO | | | TURN OFF AT DAYLIGHT OR WHEN NOT REQUIRED. CONTROLS | | | SHALL BE PHOTOSENSOR & TIME CLOCK OR ASTRONOMICAL TIME | | | SWITCH. | | | AS PER NEC THE INTERIOR OF AN UNDERGROUND (OR IN | | | CONCRETE SLAB) RACEWAY SHALL BE CONSIDERED A WET | | | LOCATION; ALL CONDUCTORS WITHIN THE RACEWAY SHALL BE | | | LISTED ACCORDINGLY. |
|