| Plan Review Notes For Permit 13060076 |
| Permit Number |
13060076 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-05 13:51:40 | 6-5-13 | | | 1. PLEASE PROVIDE A CUT SHEET FOR THE CHARGER UNIT | | | 2. WHAT IS THE DISTANCE FROM THE SOURCE OF POWER TO | | | SUB-PANEL THEN TO CHARGER? (YOUR PHOTO DOESNT HELP) | | | 3. PLEASE INDICATE CONDUCTORS AND CONDUIT SIZES | | | THROUGHOUT THE SKETCH | | | 4. IF PVC IS OUTDOORS & EXPOSED, PLEASE COMPLY TO NEC | | | 352.44 FOR EXPANSION FITTINGS | | | 5. INDICATE BREAKER SIZE FEEDING CHARGER. | | | 6. WHERE IS SUB-PANEL MOUNTED. ON WALL? ON RACK? | | | | | | VB |
|