| Plan Review Notes For Permit 13060058 |
| Permit Number |
13060058 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-05 11:43:35 | BUILDING REVISION COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- NEW TO PROVIDE EGRESS TO COMPLY WITH SEC. R310. | | | WINDOW #4 DOESN'T COMPLY. | | | | | | 2- SHEET 7.0: | | | A) BOTH WALLS ON TYPICAL WALL SECTION DETAIL NEED TO | | | SHOW FIREBLOCKING AS REQUIRED BY SEC. R302.11 OF 2010 | | | FBC-RESIDENTIAL. (AND, THIS NEEDS TO BE INSPECTED. SEC. | | | 110.3 (A)2.3 OF CITY AMENDMENTS TO FBC). | | | | | | B) TYPICAL WALL SECTION DETAIL IS MISSING THE BOTTOM | | | PLATE ON BOTH WALLS. SEC. R301.1 OF 2010 | | | FBC-RESIDENTIAL. | | | | | | 3- INSPECTIONS ARE REQUIRED BY SEC. 110.3(A)2.3. PLEASE | | | COORDINATE WITH CHIEF BUILDING INSPECTOR KEN CONRAD AT | | | (561)805-6666. REMEMBER THAT FIREBLOCKING INSPECTION IS | | | REQUIRED ALSO. SEE ITEM # 2A ABOVE. | | | | | | | | | ***REMAINDER*** | | | BUILDING PERMIT WAS APPROVED ON 2/21/13 WITH THE | | | CONDITION THAT HEATING NEED TO BE PROVIDED AS REQUIRED | | | BY SEC. R303.8. A/C CONTRACTOR NEEDS TO PROVIDE | | | COMPLETE EQUIPMENT INFORMATION UNDER A SEPARATE PERMIT. | | | PROVIDE THIS INFORMATION TO AVOID ANY CONFLICTS OR | | | DELAYS. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|