| 2013-07-10 16:18:24 | 5200 NORTH FLAGLER DRIVE |
| | PERMIT #13060053 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | REVIEW #2 COMMENTS: |
| | THE ARCHITECTURAL RESPONSE LETTER INDICATES THE BURNER |
| | WILL BE REMOVED FROM THE PROJECT; HOWEVER, THE PLANS |
| | STILL SHOW THE 4-BURNER RANGE. |
| | |
| | A COMMERCIAL OR DOMESTIC OVEN WILL REQUIRE A TYPE II |
| | MECHANICAL HOOD UNLESS THE WARMING APPLIANCE IS LISTED |
| | FOR USE WITHOUT A HOOD. |
| | |
| | THE PLANS INDICATE A DECREASE IN OCCUPANT LOAD FROM 190 |
| | PERSONS TO 64 PERSONS. PROVIDE A SEATING OR FURNITURE |
| | PLAN JUSTIFYING THE DECREASE IN OCCUPANT LOAD. |
| | |
| | THE REVIEW COMMENTS FROM REVIEW #1 HAVE NOT BEEN |
| | ADEQUATELY ADDRESSED. |
| | |
| | |
| | REVIEW #1 COMMENTS: |
| | PLANS SHOW A 4-BURNER RANGE IN THE KITCHEN AREA. |
| | COOKING OPERATIONS THAT MAY RESULT IN THE PRODUCTION OF |
| | SMOKE OR GREASE-LADEN VAPORS SHALL BE PROTECTED WITH A |
| | CLASS I MECHANICAL EXHAUST HOOD EQUIPPED WITH AN |
| | AUTOMATIC WET-CHEMICAL FIRE SUPPRESSION SYSTEM. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | PER SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF |
| | HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY |
| | (ASSEMBLY) OF THE SPACE, SHALL BE SEPARATED FROM |
| | NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR |
| | BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS |
| | SHALL BE SELF CLOSING, POSITIVE LATCHING, AND |
| | FIRE-RATED FOR AT LEAST 45-MINUTES. |
| | |
| | EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM |
| | OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL |
| | LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE |
| | ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT |
| | LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, |
| | NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF |
| | EGRESS AT FLOOR LEVEL. |
| | |
| | FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 |
| | OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON |
| | DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR |
| | LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE |
| | PANIC HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE |
| | MAIN ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED |
| | DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN |
| | STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING |
| | IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN |
| | HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE |
| | SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | MODIFICATION OF THE FIRE ALARM SYSTEM. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |