| 2013-07-02 15:11:31 | 13060023 | | | 1751 PALM BEACH LAKES BLVD. #E103 | | | INTERIOR BUILD OUT FOR AMERICAN EAGLE OUTFITTERS | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | | | | SHEET E.0.200 | | | | | | PROVIDE A DESIGNATED CLEAR WORKING SPACE AROUND THE | | | ELECTRICAL SERVICE EQUIPMENT AND PANEL BOARDS. NEC | | | 215.5, 110.26 | | | | | | SHEET E.0.300 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.22, 110.16, 110.22 | | | | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | | | | |
|