2013-07-18 10:50:522010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE RETURN AIR TRANSFER DUCTS FROM THE HABITABLE
 ROOMS ARE UNDERSIZED. FBCR M1602.4 REQUIRES THE
 TRANSFER DUCTS TO BE 1-1/2 TIMES (SQUARE INCHES) THE
 CROSS SECTIONAL AREA OF OF THE SUPPLY DUCT ENTERING THE
 ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AN
 UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
  