| Plan Review Notes For Permit 13060004 |
| Permit Number |
13060004 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-18 10:50:52 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE RETURN AIR TRANSFER DUCTS FROM THE HABITABLE | | | ROOMS ARE UNDERSIZED. FBCR M1602.4 REQUIRES THE | | | TRANSFER DUCTS TO BE 1-1/2 TIMES (SQUARE INCHES) THE | | | CROSS SECTIONAL AREA OF OF THE SUPPLY DUCT ENTERING THE | | | ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AN | | | UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER RETURN | | | AIR BALANCE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|