| Plan Review Notes For Permit 13051115 |
| Permit Number |
13051115 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-06-03 15:51:49 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | SEE RAS 117: | | | | | | 1. REVISE SPECIFICATION TO STATE WHETHER THE ROWS | | | SPECIFIED INCLUDE OR EXCLUDE THE LAP ROW. | | | | | | 2. ZONE 2 AND ZONE 3, SEE RAS 117 10.4.5, FRACTIONS TO | | | BE ROUNDED DOWN TO THE NEXT WHOLE NUMBER. | | | | | | 3. ZONE 3, SEE RAS 117 8.1, MINIMUM FASTENER SEPARATION | | | SHALL NOT BE LESS THAN 4 IN. O.C. | | | |
|