| Notes |
| Date |
Text |
| 2013-06-01 14:11:47 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. TWO DIFFERENT ASSEMBLIES WERE INCLUDED IN THE NOA | | | SUBMITTED. BOTH HAVE GENERAL LIMITATION #9, WHICH DOES | | | NOT ALLOW ENHANCED FASTENING. SELECT AN ASSEMBLY WHICH | | | EITHER MEETS ZONE 3 (WORST CASE) DESIGN PRESSURES OR | | | WHICH INCLLUDES GENERAL LIMITATION #7. | | | | | | 2. IF AN ASSEMBLY WITH GENERAL LIMITATION #7 IS | | | SELECTED AND DOES NOT MEET WORST CASE DESIGN PRESSURE, | | | RAS 117 CALCULATIONS PREPARED BY AN ARCHITECT, | | | ENGINEER, OR REGISTERED ROOF CONSULTANT WILL BE | | | REQUIRED. SEE LAST PAGE OF NOA, GENERAL LIMITATION #7, | | | AND FBC R 301. | | | | | | |
|