| Plan Review Notes For Permit 13051103 |
| Permit Number |
13051103 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2013-09-03 11:52:05 | PASS PROVISO. | | | REVISION REQUIRED FOR ROUGH INSPECTION. | | | 1) PROVIDE DUCT SIZE FOR OUTSIDE AIR DUCT | | | ON 10 TON RTU. | | | 2) RELOCATED 5 TON RTU AND EXISTING | | | 3 TON RTU PROVIDE SEPARATE DAMPERS FOR | | | OUTSIDE AIR. | | | 3) PROVIDE SUPPLY GRILLE SIZE ON THE PLANS. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|