| Plan Review Notes For Permit 13051103 |
| Permit Number |
13051103 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-05 09:30:20 | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. IF THE OCCUPANCY TYPE IS A-3, THEN A SERVICE SINK IS | | | REQUIRED. | | | FBC PLUMBING 2010 TABLE 403.1 | | | | | | 2. SHEETS P2.1 & P5.1 IF THE RESTROOM SANITARY IS TWO | | | CURCUIT VENT SYSTEMS, A VERTICAL DRY VENT IS REQUIRED | | | BETWEEN THE TWO MOST UPSTREAM FLOOR FIXTURES. | | | 911.2 VENT CONNECTION. | | | THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN | | | THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL | | | CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED | | | IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE | | | SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|