| Date |
Text |
| 2013-07-03 17:51:15 | BUILDING PLAN REVIEW |
| | PERMIT: 13051103 |
| | ADD: 911 VILLAGE BLVD |
| | CONT: KARNS & BALDWIN INNOVATIVE BUILDERS |
| | TEL: (561)805-7528 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: JULY 03/2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 1 PLEASE CORRECT OCCUPANCY TYPE TO A-3, 2010 |
| | FBC-B SECTION 303.1. |
| | |
| | 2) SHEET 2 INDICATES THE USE OF CLOSED CELL ICYENE R-8 |
| | INSULATION APPLIED TO THE BOTTOM OF THE BAR JOIST. |
| | PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION FOR |
| | ICYENE PROVIDING HOW THICK THE INSULATION WILL NEED TO |
| | BE APPLIED TO ACHIEVE A R-8 VALUE. |
| | 2A) PROVIDE PRODUCT COMPLIANCE FOR: |
| | FBC-B 2603.5.2 THERMAL BARRIER. ANY FOAM PLASTIC |
| | INSULATION SHALL BE SEPARATED FROM THE BUILDING |
| | INTERIOR BY A THERMAL BARRIER MEETING THE PROVISIONS OF |
| | SECTION 2603.4, UNLESS SPECIAL APPROVAL IS OBTAINED ON |
| | THE BASIS OF SECTION 2603.9. |
| | |
| | FBC-B 2603.9 SPECIAL APPROVAL. |
| | FOAM PLASTIC SHALL NOT BE REQUIRED TO COMPLY WITH THE |
| | REQUIREMENTS OF SECTIONS 2603.4 THROUGH 2603.7 WHERE |
| | SPECIFICALLY APPROVED BASED ON LARGE-SCALE TESTS SUCH |
| | AS, BUT NOT LIMITED TO, NFPA 286 (WITH THE |
| | ACCEPTANCE CRITERIA OF SECTION 803.2), FM 4880, UL 1040 |
| | OR UL 1715. SUCH TESTING SHALL BE RELATED TO THE ACTUAL |
| | END-USE CONFIGURATION AND BE PERFORMED ON THE FINISHED |
| | MANUFACTURED FOAM PLASTIC |
| | ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED FOR USE. |
| | FOAM PLASTICS THAT ARE USED AS INTERIOR FINISH ON THE |
| | BASIS OF SPECIAL TESTS SHALL ALSO CONFORM TO THE FLAME |
| | SPREAD REQUIREMENTS OF CHAPTER 8. ASSEMBLIES |
| | TESTED SHALL INCLUDE SEAMS, JOINTS AND OTHER TYPICAL |
| | DETAILS USED IN THE INSTALLATION OF THE ASSEMBLY AND |
| | SHALL BE TESTED IN THE MANNER INTENDED FOR USE. |
| | |
| | 2B) 2603.7 PLENUMS. FOAM PLASTIC INSULATION SHALL NOT |
| | BE USED AS INTERIOR WALL OR CEILING FINISH IN PLENUMS |
| | EXCEPT AS PERMITTED IN SECTION 2604 OR WHEN PROTECTED |
| | BY A THERMAL BARRIER IN ACCORDANCE WITH SECTION 2603.4. |
| | |
| | 2C) DEPENDING ON THE METHOD OF APPLICATION THIS CODE |
| | SECTION MAY ALSO HAVE SOME REVEVANCE, ONCE THE |
| | MANUFACTURERS SPECS AND TYPE OF APPLICATION IS KNOWN. |
| | 2603.4.1.6 ATTICS AND CRAWL SPACES. |
| | WITHIN AN ATTIC OR CRAWL SPACE WHERE ENTRY IS MADE ONLY |
| | FOR SERVICE OF UTILITIES, FOAM PLASTIC INSULATION SHALL |
| | BE PROTECTED AGAINST IGNITION BY 11/2-INCH-THICK (38 |
| | MM) MINERAL FIBER INSULATION; 1/4-INCH-THICK (6.4 MM) |
| | WOOD STRUCTURAL PANEL, PARTICLEBOARD OR HARDBOARD; |
| | 3/8-INCH (9.5 MM) GYPSUM WALLBOARD, CORROSION-RESISTANT |
| | STEEL HAVING A BASE METAL THICKNESS OF 0.016 INCH (0.4 |
| | MM) OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A |
| | MANNER THAT THE FOAM PLASTIC INSULATION IS NOT EXPOSED. |
| | THE PROTECTIVE COVERING SHALL BE CONSISTENT WITH THE |
| | REQUIREMENTS FOR THE TYPE OF CONSTRUCTION. |
| | |
| | 3) SHEET 2 SHOWS A 42 INCH HIGH JUICE BAR, PLEASE |
| | PROVIDE HOW COMPLIANCE WITH SECTION 2010 FBC-B 902.3 |
| | HEIGHT. THE TOPS OF DINING SURFACES AND WORK SURFACES |
| | SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |