2013-06-07 16:34:34****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. THE ASSEMBLY SELECTED, W15 ON PAGE 6, DOES NOT MEET
 DESIGN PRESSURE REQUREMENTS FOR THIS ZONE 3 FOR THIS
 JOB. AS MRH WAS NOT PROVIDED, EXACT DESIGN PRESSURES
 CANNOT BE PROVIDED. SEE FBC R TABLE 301.2(2) AND (3).
  
 FOR EXPOSURE C, MRH 20', ZONE 2 HAS A REQUIREMENT OF
 -67.8PSF, ****ZONE 3 = -102PSF****.
  
 THE ASSEMBLY SELECTED HAS A LIMITATION OF -90 PSF.
  