2013-06-01 14:20:43****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THE ASSEMBLY SELECTED, W9 ON PAGE 6, DOES NOT MEET
 DESIGN PRESSURE REQUREMENTS FOR THIS JOB. AS MRH WAS
 NOT PROVIDED, EXACT DESIGN PRESSURES CANNOT BE
 PROVIDED. SEE FBC R TABLE 301.2(2) AND (3).
  
 FOR EXPOSURE C, MRH 20', ZONE 2 HAS A REQUIREMENT OF
 -67.8PSF, ZONE 3 = -102PSF.
  
 THE ASSEMBLY SELECTED HAS A LIMITATION OF -52.5 PSF.
  