| Plan Review Notes For Permit 13051102 |
| Permit Number |
13051102 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-01 14:20:43 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. THE ASSEMBLY SELECTED, W9 ON PAGE 6, DOES NOT MEET | | | DESIGN PRESSURE REQUREMENTS FOR THIS JOB. AS MRH WAS | | | NOT PROVIDED, EXACT DESIGN PRESSURES CANNOT BE | | | PROVIDED. SEE FBC R TABLE 301.2(2) AND (3). | | | | | | FOR EXPOSURE C, MRH 20', ZONE 2 HAS A REQUIREMENT OF | | | -67.8PSF, ZONE 3 = -102PSF. | | | | | | THE ASSEMBLY SELECTED HAS A LIMITATION OF -52.5 PSF. | | | |
|