2013-06-14 14:14:451400 VILLAGE BOULEVARD
 PERMIT #13051091
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 241 (TABLE 4.2.1), THE TEMPORARY MODULAR
 BUILDING SHALL BE LOCATED AT LEAST 50 FEET AWAY FROM
 ADJACENT STRUCTURES. CURRENTLY THERE APPEARS TO ONLY BE
 APPROXIMATELY 20 FEET OF SEPARATION.
  
 PROVIDE STAIR AND HANDRAIL DETAILS. HANDRAILS ARE
 REQUIRED ON BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE
 LOCATED NOT LESS THAN 34 INCHES AND NOT MORE THAN 38
 INCHES ABOVE THE SURFACE OF THE TREAD, MEASURED
 VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE
 OF THE TREAD. HANDRAIL ENDS SHALL BE RETURNED TO THE
 WALL OR FLOOR OR SHALL TERMINATE AT NEWEL POSTS.
 HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF NOT
 LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES. STAIR
 RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN
 HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A
 MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE
 ACCUMULATION OF WATER.
  
 PROVIDE PORTABLE FIRE EXTINGUISHER(S). EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  