Plan Review Notes
Plan Review Notes For Permit 13051078
Permit Number 13051078
Review Stop E
Sequence Number 2
Notes
Date Text
2013-08-06 15:37:44POLE ANALYSIS IS NOT SEALED BY A FLORIDA REGISTERED
 ENGINEER. PROVIDE LISTING INFORMATION FOR LUMINAIRES
 FROM A RECOGNIZED TESTING LAB. SECURITY CAMERAS REQUIRE
 A SEPARATE PERMIT. ADDRESS CAMERA WINDLOAD ON POLES
 THAT WILL HAVE CAMERAS. SECTION 4 APPEARS TO BE THE
 ONLY SECTION PROVIDED THAT IS RELATED TO SITE LIGHTING.
 DIFFERENT ENGINEERS HAVE SEALED THE PAGES RELATED TO
 THE LIGHTING, ATTACHEMENT, WINDLOAD AND BASES. PLEASE
 PROVIDE CONFIRMATION THE ENGINEERS ARE IN AGREEMENT
 THAT THE POLE BASE DETAIL WILL PROVIDE THE NEEDED
 UPLIFT, OVERTURN AND OTHER LOADS ASSOCIATED WITH THE
 POLES SPECIFIED.