| Plan Review Notes For Permit 13051078 |
| Permit Number |
13051078 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-08-06 15:37:44 | POLE ANALYSIS IS NOT SEALED BY A FLORIDA REGISTERED | | | ENGINEER. PROVIDE LISTING INFORMATION FOR LUMINAIRES | | | FROM A RECOGNIZED TESTING LAB. SECURITY CAMERAS REQUIRE | | | A SEPARATE PERMIT. ADDRESS CAMERA WINDLOAD ON POLES | | | THAT WILL HAVE CAMERAS. SECTION 4 APPEARS TO BE THE | | | ONLY SECTION PROVIDED THAT IS RELATED TO SITE LIGHTING. | | | DIFFERENT ENGINEERS HAVE SEALED THE PAGES RELATED TO | | | THE LIGHTING, ATTACHEMENT, WINDLOAD AND BASES. PLEASE | | | PROVIDE CONFIRMATION THE ENGINEERS ARE IN AGREEMENT | | | THAT THE POLE BASE DETAIL WILL PROVIDE THE NEEDED | | | UPLIFT, OVERTURN AND OTHER LOADS ASSOCIATED WITH THE | | | POLES SPECIFIED. |
|