| 2013-07-01 10:47:33 | 13051078 | | | 4001 S DIXIE HWY | | | WALGREEN?S SITE LIGHTING | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE SPECIFICATIONS AND THE LISTING FROM A | | | NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) FOR THE | | | POLES AND FIXTURES. NEC 110.3 | | | | | | WIND LOAD ENGINEERING FOR THE LIGHT POLES AND FIXTURES | | | NEEDS TO REFERENCE THE ACTUAL FIXTURE TYPE OR MODEL | | | WITH ITS EPA AND ALSO VERIFY THE EXISING FOOTER IS | | | STRUCTURALLY ADEQUATE. FBC 1609.1 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | | | | |
|