| 2013-06-08 11:15:21 | 2101 CENTERPARK DRIVE - WEST: SUITE #110 |
| | PERMIT #13051060 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PLANS INDICATE A BUSINESS OCCUPANCY; HOWEVER, THE |
| | COMBINED SIZE OF THE TWO ASSEMBLY USE CONFERENCE ROOMS |
| | IS APPROXIMATELY 1,155 SQ.FT. OR 17% OF SUITE #110 |
| | (6,620 SQ.FT.). FOR THE ASSEMBLY SPACES TO BE |
| | CONSIDERED ACCESSORY TO THE BUSINESS OCCUPANCY, THE |
| | ASSEMBLY SPACES CANNOT EXCEED 10% OF THE SUITE AREA. |
| | |
| | THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 |
| | OF NFPA 101 FLORIDA EDITION 2009. FOR NON-SEPARATED |
| | MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE |
| | SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO |
| | THE BUILDING. |
| | |
| | PROVIDE AN OCCUPANT LOAD BREAKDOWN FOR THE SUITE. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | ELECTRICAL: EMERGENCY ILLUMINATION SHALL BE PROVIDED |
| | FOR A MINIMUM OF 1.5 HOURS IN THE EVENT OF FAILURE OF |
| | NORMAL LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE |
| | ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT |
| | LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, |
| | NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF |
| | EGRESS AT FLOOR LEVEL. |
| | |
| | ELECTRICAL: NO ENGINEERED FIRE ALARM DRAWINGS |
| | SUBMITTED. PER FBC SECTION 907.1.1 CONSTRUCTION |
| | DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR FIRE ALARM |
| | SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL." |
| | |