Plan Review Notes
Plan Review Notes For Permit 13051030
Permit Number 13051030
Review Stop M
Sequence Number 4
Notes
Date Text
2013-09-18 18:03:072010 FBC
  
 DENIED BY BUILDING
  
 1) THE NEW EQUIPMENT SIZING CALCULATIONS AND ENERGY
 CALCULATIONS DO NOT MATCH THE MECHANICAL PLANS. THE NEW
 CALCULATIONS SPECIFY 2 - TON UNITS ON BOTH FLOORS. THE
 OLD EQUIPMENT SIZING CALCULATIONS AND THE EQUIPMENT
 SCHEDULE ON THE MECHANICAL PLANS SPECIFY A 2 - TON UNIT
 ON THE FIRST FLOOR AND A 2.5 TON UNIT ON THE SECOND
 FLOOR. THE EQUIPMENT SCHEDULE ON THE PLANS HAS TO MATCH
 THE SIZING CALCULATIONS AND THE ENERGY CALC. FORM. FBC
 ENERGY CONSERVATION SECTION 405 & FBCR M1401.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW