| Plan Review Notes For Permit 13051030 |
| Permit Number |
13051030 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2013-09-18 18:03:07 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE NEW EQUIPMENT SIZING CALCULATIONS AND ENERGY | | | CALCULATIONS DO NOT MATCH THE MECHANICAL PLANS. THE NEW | | | CALCULATIONS SPECIFY 2 - TON UNITS ON BOTH FLOORS. THE | | | OLD EQUIPMENT SIZING CALCULATIONS AND THE EQUIPMENT | | | SCHEDULE ON THE MECHANICAL PLANS SPECIFY A 2 - TON UNIT | | | ON THE FIRST FLOOR AND A 2.5 TON UNIT ON THE SECOND | | | FLOOR. THE EQUIPMENT SCHEDULE ON THE PLANS HAS TO MATCH | | | THE SIZING CALCULATIONS AND THE ENERGY CALC. FORM. FBC | | | ENERGY CONSERVATION SECTION 405 & FBCR M1401.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|