| Notes |
| Date |
Text |
| 2013-08-05 07:17:12 | 2010 FBC | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED | | | BY FBC ENERGY SECTIONS 101.4.1 AND 401.2 OR SHOW | | | COMPLIANCE WITH PRESCRIPTIVE REQUIREMENTS. THE FBC | | | ENERGY CONSERVATION TABLE 101.4.1 FOR RENOVATIONS, | | | SPECIFIES THAT THE MINIMUM CODE ENVELOPE, EQUIPMENT AND | | | LIGHTING EFFICIENCY LEVELS SHALL BE MET FOR COMPONENTS | | | BEING CHANGED. THE FORM THAT WAS SUBMITTED IS OUTDATED | | | (FORM 600C-01) AND IS FOR CENTRAL FLORIDA , THE WRONG | | | CLIMATE ZONE. PLEASE SUBMIT TWO COPIES OF FORM 402-2010 | | | OR THE COMPLIANCE REPORT REQUIRED BY SECTION 405 | | | SHOWING COMPLIANCE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|