Plan Review Notes
Plan Review Notes For Permit 13051030
Permit Number 13051030
Review Stop M
Sequence Number 2
Notes
Date Text
2013-08-05 07:17:122010 FBC
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY SECTIONS 101.4.1 AND 401.2 OR SHOW
 COMPLIANCE WITH PRESCRIPTIVE REQUIREMENTS. THE FBC
 ENERGY CONSERVATION TABLE 101.4.1 FOR RENOVATIONS,
 SPECIFIES THAT THE MINIMUM CODE ENVELOPE, EQUIPMENT AND
 LIGHTING EFFICIENCY LEVELS SHALL BE MET FOR COMPONENTS
 BEING CHANGED. THE FORM THAT WAS SUBMITTED IS OUTDATED
 (FORM 600C-01) AND IS FOR CENTRAL FLORIDA , THE WRONG
 CLIMATE ZONE. PLEASE SUBMIT TWO COPIES OF FORM 402-2010
 OR THE COMPLIANCE REPORT REQUIRED BY SECTION 405
 SHOWING COMPLIANCE.
  