| Plan Review Notes For Permit 13051030 |
| Permit Number |
13051030 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-11 15:05:17 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED | | | BY FBC ENERGY SECTIONS 101.4.1 AND 401.2 OR SHOW | | | COMPLIANCE WITH PRESCRIPTIVE REQUIREMENTS. | | | | | | 2) THE RETURN AIR FOR THE FIRST FLOOR APPEARS TO BE | | | THROUGH THE LOUVERED DOOR OF THE A/H CLOSET LOCATED IN | | | THE FLEX ROOM. THIS ROOM HAS DOORS THAT WHEN CLOSED | | | WILL RESTRICT RETURN AIR FROM THE OTHER AREAS OF THE | | | FLOOR. SHOW COMPLIANCE WITH FBCR M1602.4 FOR REQUIRED | | | BALANCED RETURN AIR. | | | | | | 3) THE RETURN AIR AT THE SECOND FLOOR DOES NOT COMPLY | | | WITH FBCR M1602.4 FOR REQUIRED BALANCED RETURN AIR FOR | | | THE BEDROOMS AND MASTER SUITE. PLEASE CORRECT. | | | | | | 4) SPECIFY THE LOCATION OF THE SECOND FLOOR AIR | | | HANDLER. IF IT IS LOCATED IN THE ATTIC, SHOW THAT IT | | | COMPLIES WITH FBCR M1305.1.3. | | | | | | 5) ON SHEET AIR-1 A 12 X 6 GRILL IS SHOWN NEAR THE | | | KITCHEN EATING AREA WITH NO DUCT CONNECTED TO IT AND ON | | | SHEET AIR-2 THE DUCT CONNECTED TO THE 12 X 6 GRILL IN | | | BED ROOM # 2 IS NOT SHOWN. PLEASE CORRECT. CITY | | | AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | | | | | | | |
|