Plan Review Notes For Permit 13051017
Permit Number 13051017
Review Stop B
Sequence Number 2
Notes
Date Text
2013-07-23 16:54:09REVISION IS REQUIRED
  
 THE ELEVATION CERTIFICATE THAT WAS SUBMITTED INDICATES
 THAT THE FLOOR OF THE GARAGE, AS WELL AS, SOME OF THE
 EQUIPMENT SERVICING THE BUILDING IS BELOW THE REQUIRED
 FLOOD ELEVATION OF 7.5' BFE WHICH INCLUDES THE 6"
 FREEBOARD REQUIRED BY CITY ORDINANCE. ALL EQUIPMENT IS
 REQUIRED TO BE RAISED TO OR ABOVE 7.5' BFE AND THE
 GARAGE IS REQUIRED TO COMPLY BY RAISING THE FINISH
 FLOOR OR INSTALLING FLOOD VENTS PER FBC R322.