| Plan Review Notes For Permit 13051017 |
| Permit Number |
13051017 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-07-23 16:54:09 | REVISION IS REQUIRED | | | | | | THE ELEVATION CERTIFICATE THAT WAS SUBMITTED INDICATES | | | THAT THE FLOOR OF THE GARAGE, AS WELL AS, SOME OF THE | | | EQUIPMENT SERVICING THE BUILDING IS BELOW THE REQUIRED | | | FLOOD ELEVATION OF 7.5' BFE WHICH INCLUDES THE 6" | | | FREEBOARD REQUIRED BY CITY ORDINANCE. ALL EQUIPMENT IS | | | REQUIRED TO BE RAISED TO OR ABOVE 7.5' BFE AND THE | | | GARAGE IS REQUIRED TO COMPLY BY RAISING THE FINISH | | | FLOOR OR INSTALLING FLOOD VENTS PER FBC R322. |
|