2013-07-02 16:57:35MECHANICAL PROVISO
  
 1) REVISED PLANS SHOWING THE LOCATION, DUCT SIZE, GRILL
 SIZE AND CFMS WILL BE REQUIRED FOR ANY NEW DUCTWORK.
  
 2) THE RENOVATION IS REQUIRED TO COMPLY WITH FBC ENERGY
 CONSERVATION SECTION 101.4.1 AND TABLE 101.4.1. MINIMUM
 CODE ENVELOPE, EQUIPMENT AND LIGHTING EFFICIENCY LEVELS
 SHALL BE MET FOR COMPONENTS BEING CHANGED.