| Plan Review Notes For Permit 13051017 |
| Permit Number |
13051017 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-02 16:57:35 | MECHANICAL PROVISO | | | | | | 1) REVISED PLANS SHOWING THE LOCATION, DUCT SIZE, GRILL | | | SIZE AND CFMS WILL BE REQUIRED FOR ANY NEW DUCTWORK. | | | | | | 2) THE RENOVATION IS REQUIRED TO COMPLY WITH FBC ENERGY | | | CONSERVATION SECTION 101.4.1 AND TABLE 101.4.1. MINIMUM | | | CODE ENVELOPE, EQUIPMENT AND LIGHTING EFFICIENCY LEVELS | | | SHALL BE MET FOR COMPONENTS BEING CHANGED. |
|