| Date |
Text |
| 2013-07-03 09:48:19 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THIS PRE-FIRM STRUCTURE IS LOCATED IN AN A5 FLOOD |
| | ZONE. THE VALUE OF THE WORK IS $1,000,000.00 WHICH IS |
| | MORE THAN 50% OF THE IMPROVEMENT VALUE OF THE STRUCTURE |
| | LISTED ON THE PBC PROPERTY APPRAISER'S WEB SITE. THIS |
| | IS CONSIDERED A SUBSTANTIAL IMPROVEMENT AND THE |
| | EXISTING STRUCTURE IS REQUIRED TO HAVE IT'S LOWEST |
| | FLOOR ELEVATED TO OR ABOVE THE BFE. THE BFE FOR THIS |
| | LOCATION IS 7 FEET PLUS THE 6 INCH FREE BOARD PER FEMA |
| | FLOOD INSURANCE RATE MAPS AND CITY OF WPB FLOOD |
| | ORDINANCE. PLEASE SUBMIT AN ELEVATION CERTIFICATE |
| | SHOWING THAT THE EXISTING LOWEST FLOOR ELEVATIONS ARE |
| | AT OR ABOVE 7' 6" BFE OR SUBMIT A FLOOR PLAN SHOWING |
| | PROPOSED FIRST FLOOR ELEVATIONS WITH DETAILS OF HOW THE |
| | FLOORS WILL BE ELEVATED. CITY AMENDMENTS 107.2.1 AND |
| | FBC R322. |
| | |
| | 2) THE OCCUPANCY TYPE SPECIFIED ON SHEET CVR IS |
| | INCORRECT. THIS IS A SINGLE FAMILY RESIDENCE THE |
| | CORRECT OCCUPANCY TYPE IS R3. FBC SECTION 310 |
| | |
| | 3) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE NEW |
| | EXTERIOR DOOR THAT IS TO BE REPLACED AS REQUIRED BY DCA |
| | RULE 9N-3. |
| | |
| | 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT. CITY AMENDMENTS 107.3.4 |
| | |
| | 5) THE DOOR FROM THE GARAGE TO THE LIVING SPACE IS |
| | REQUIRED TO COMPLY WITH FBC R302.5.1. |
| | |
| | 6) THE DWELLING/GARAGE FIRE SEPARATION SHALL COMPLY |
| | WITH FBC R302.6. |
| | |
| | IN ORDER TO SPEED THE REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS HAVE |
| | BEEN ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |