Plan Review Notes
Plan Review Notes For Permit 13051017
Permit Number 13051017
Review Stop B
Sequence Number 1
Notes
Date Text
2013-07-03 09:48:192010 FBC
  
 DENIED BY BUILDING
  
 1) THIS PRE-FIRM STRUCTURE IS LOCATED IN AN A5 FLOOD
 ZONE. THE VALUE OF THE WORK IS $1,000,000.00 WHICH IS
 MORE THAN 50% OF THE IMPROVEMENT VALUE OF THE STRUCTURE
 LISTED ON THE PBC PROPERTY APPRAISER'S WEB SITE. THIS
 IS CONSIDERED A SUBSTANTIAL IMPROVEMENT AND THE
 EXISTING STRUCTURE IS REQUIRED TO HAVE IT'S LOWEST
 FLOOR ELEVATED TO OR ABOVE THE BFE. THE BFE FOR THIS
 LOCATION IS 7 FEET PLUS THE 6 INCH FREE BOARD PER FEMA
 FLOOD INSURANCE RATE MAPS AND CITY OF WPB FLOOD
 ORDINANCE. PLEASE SUBMIT AN ELEVATION CERTIFICATE
 SHOWING THAT THE EXISTING LOWEST FLOOR ELEVATIONS ARE
 AT OR ABOVE 7' 6" BFE OR SUBMIT A FLOOR PLAN SHOWING
 PROPOSED FIRST FLOOR ELEVATIONS WITH DETAILS OF HOW THE
 FLOORS WILL BE ELEVATED. CITY AMENDMENTS 107.2.1 AND
 FBC R322.
  
 2) THE OCCUPANCY TYPE SPECIFIED ON SHEET CVR IS
 INCORRECT. THIS IS A SINGLE FAMILY RESIDENCE THE
 CORRECT OCCUPANCY TYPE IS R3. FBC SECTION 310
  
 3) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOOR THAT IS TO BE REPLACED AS REQUIRED BY DCA
 RULE 9N-3.
  
 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4
  
 5) THE DOOR FROM THE GARAGE TO THE LIVING SPACE IS
 REQUIRED TO COMPLY WITH FBC R302.5.1.
  
 6) THE DWELLING/GARAGE FIRE SEPARATION SHALL COMPLY
 WITH FBC R302.6.
  
 IN ORDER TO SPEED THE REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS HAVE
 BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]