| 2013-06-29 19:44:17 | O LAMBERTON DRIVE |
| | PERMIT #13051012 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| | (2009 EDITION WITH FLORIDA AMENDMENTS.) |
| | |
| | NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION. |
| | |
| | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK |
| | SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH |
| | AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE |
| | DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED |
| | EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION |
| | AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE |
| | SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING |
| | MATERIALS SHALL BE PROVIDED. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | NO FIRE FLOW CALCULATIONS OR CIVIL ENGINEERING PLANS |
| | SUBMITTED SHOWING FIRE WATER, FIRE HYDRANTS, FIRE |
| | DEPARTMENT ACCESS ROADS (FIRE LANES), ETC. PER SECTION |
| | 18.3.4.1 (NFPA 1), FIRE HYDRANTS AND FIRE DEPARTMENT |
| | CONNECTIONS SHALL BE PROVIDED WITH CLEARANCES OF 7'-6" |
| | TO THE FRONT AND SIDES AND 4' TO THE BACKSIDE. PER |
| | SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT ACCESS |
| | ROADS SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE |
| | APPARATUS WEIGHING AT LEAST 32 TONS. ACCESS ROADS SHALL |
| | HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND |
| | AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 |
| | FEET 6 INCHES. PER SECTION 18.2.3.5.3 (NFPA 1), FIRE |
| | LANES SHALL BE MARKED WITH FREESTANDING SIGNS READING, |
| | "FIRE LANE - NO PARKING BY ORDER OF THE FIRE |
| | DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE |
| | BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF |
| | SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS |
| | SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED |
| | A MAXIMUM OF 60 FEET APART. |
| | |
| | SHEET A0.10: PROVIDE A KNOX KEY SWITCH TO ALLOW GATE |
| | ACCESS TO EMERGENCY RESPONDERS. KEY SWITCH CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | SHEET A0.10 - BUILDING #4: DEAD-END FIRE DEPARTMENT |
| | ACCESS ROADS IN EXCESS OF 150 FEET IN LENGTH SHALL BE |
| | PROVIDED WITH APPROVED PROVISIONS FOR THE FIRE |
| | APPARATUS TO TURN AROUND. |
| | |
| | SHEET F1.001: ALL FIRE SPRINKLER SYSTEMS SHALL BE |
| | MONITORED BY AN APPROVED SUPERVISING STATION IN |
| | ACCORDANCE WITH NFPA 72. |
| | |
| | SHEET F1.11 (TYPICAL): THE APARTMENT BUILDING CORRIDORS |
| | WILL BE REQUIRED TO BE PROTECTED BY SPRINKLERS BECAUSE |
| | THE CORRIDORS ARE NOT AT LEAST 50% OPEN. THE CORRIDOR |
| | SPRINKLERS ARE PERMITTED TO BE RESIDENTIAL STYLE PER |
| | NFPA 13R. |
| | |
| | SHEET F6.01: THE SPRINKLER RISER DETAIL INDICATES THE |
| | FIRE DEPARTMENT CONNECTION CONNECTED TO THE UNDERGROUND |
| | FIRE MAIN. CHECK VALVES WILL BE NEEDED IN THE |
| | UNDERGROUND FIRE MAIN PIPING TO PREVENT THE FIRE |
| | DEPARTMENT FROM PRESSURIZING THE UNDERGROUND FIRE MAIN |
| | LOOP SUPPLYING THE SITE. RECOMMEND CONNECTING THE FIRE |
| | DEPARTMENT CONNECTION DOWNSTREAM OF THE RISER BUTTERFLY |
| | VALVE. |
| | |
| | SHEET E401: SMOKE ALARM MISSING FROM OUTSIDE OF BEDROOM |
| | DOORS IN UNIT A01. |
| | |
| | SHEET E402: SMOKE ALARM MISSING FROM OUTSIDE OF WEST |
| | BEDROOM DOORS IN UNIT B02. |
| | |
| | |
| | NOTES: |
| | NO FIRE HYDRANTS PROVIDED ON SOUTH SIDE OF BUILDINGS |
| | #10 AND #11. |
| | |
| | FIRE DEPARTMENT CONNECTIONS ARE TO BE LOCATED WITHIN |
| | 150 FEET OF A FIRE HYDRANT. |
| | |
| | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE |
| | DEPARTMENT CONNECTION. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |