| 2013-08-05 11:26:40 | SHEET E1001 - ARE "POWER COMPANY FEEDERS" PROVIDED BY | | | FPL OR CUSTOMER? IF BY CUSTOMER, COMPLY WITH 240.4 | | | NOTES ADDED TO PLANS FOR LOCATIONS OF SMOKE ALARMS IN | | | UNITS TO BE PER MANUFACTURERS INSTRUCTIONS AND TO | | | PROVIDE BEST EARLY DETECTION WITHOUT NUISANCE ALARMING | | | ALL CONDUCTORS TO BE SIZED PER NEC 310.15 AND | | | ASSOCIATED NOTES | | | CONDUCTOR SETS PROTECTED IN EXCESS OF 800 TO BE FULL | | | SIZE RATED FOR THE OVERCURRENT DEVICE | | | SIZE GROUNDING ELECTRODE CONDUCTORS BASED ON TOTAL | | | SERVICE CONDUCTOR SIZE (250.66) AND EQUIPMENT GROUNDING | | | CONDUCTORS BASED ON OCP (250.122) | | | FIELD INSPECTOR TO VERIFY COMPLIANCE WITH FAIR HOUSING | | | GUIDELINES FOR HEIGHT OF RECEPTACLES AND SWITCHES | | | NUMEROUS NOTES ADDED TO PLANS AS "TYPICAL" NOTES TO BE | | | COMPLIED WITH | | | | | | |
|