| Plan Review Notes For Permit 13050993 |
| Permit Number |
13050993 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-03 11:51:42 | 6-3-13 | | | | | | ALL CONDUCTORS IN CONDUITS ARE CONSIDERED BEING IN A | | | WET LOCATION | | | | | | NEC 300.5 B (THE INTERIOR OF ENCLOSURES OR RACEWAYS | | | INSTALLED UNDERGROUND SHALL BE CONSIDERED AS "WET | | | LOCATION. | | | | | | VB |
|